UM-1097
Revision B
98
Holding Registers
Type
Channel First
Last
Block
Size
Read
FC
Write
FC
Notes
Alarm
Reset
N/A
40001 40001 N/A
3
6, 16 Simulates the alarm reset
button. Write a value of 1 to
activate.
System
Name
N/A
40010 40017 N/A
3
6, 16 Character string, 2 characters
per register
Date, Year N/A
40020 40020 N/A
3
6, 16 0000 - 9999
Date, Mon N/A
40021 40021 N/A
3
6, 16 0 – 12
Date, Day N/A
40022 40022 N/A
3
6, 16 0 – 31
Time,
Hour
N/A
40023 40023 N/A
3
6, 16 0 – 23
Time, Min N/A
40024 40024 N/A
3
6, 16 0 – 59
Time, Sec N/A
40025 40025 N/A
3
6, 16 0 – 59
Warmup
Time
N/A
40027 40027 N/A
3
6, 16 Time in minutes. 0 – 5
Cal Purge
Time
N/A
40028 40028 N/A
3
6, 16 Time in minutes. 0 – 5
Block
Negative
N/A
40029 40029 N/A
3
6, 16 No = 0, Yes = 1