LOG ENTRY
HeatNet Control V3
Page 85
Line 4 Log Entries:
To access the Log Files, press and hold, the
“Back”
button for 5 seconds, the control will beep once. There are three menu
options,
SETUP, ADVANCED SETUP,
and
VIEW LOG
. Place the curser in front of the
VIEW LOG
menu item and press
“Select”.
The following table lists the messages on line # 4 of the log’s display.
Line # 4 Message
Description
SETBACK IS ACTIVE
SETBACK EXPIRED
If any of the (4) temperature setbacks are active these log entries will be
displayed in the log.
NO LOCAL FLOW
NO SYSTEM FLOW
If the test for flow fails these log entries will be displayed. The flow proving
switches are wired to J11A and J11B.
COMBUSTION AIR FAIL
If the combustion air damper is used and does not prove across J10B
DAMPER or J12B DAMPER, this message is displayed.
SYSTEM RESET -- ----
O: stack overflow,
U: Stack Underflow ( both are software faults)
R: Reset Instruction ( Firmware or Default load),
W: Watchdog ( Firmware code ran erroneous code and
rebooted),
P: Power-ON (Power switch toggled),
B: Brown-out ( Microcontroller saw a voltage less than 4.5
VDC)
When the control is reset, this log entry captures the reason the reset occurred.