DHW METHODS
HeatNet Control V3
Page 52
If
SHARING
is set to
NO CYCLE,
a hot swap
will occur. A hot swap is when the boiler is
running in space heating mode and does not need
to be shut down. The DHW pump/valve will be
energized without the boiler stopping. Once the
DHW cycle has completed, the boiler will stop
and wait to be called again for either space
heating or DHW heating. A shutdown always
occurs after a DHW cycle completes.
10.
Set the
LOCAL PUMP/VALVE OFF
to
NO
.
This will leave the local pump on during a DHW
heating cycle (backwards compatibility).
Setting this value to
YES
, will shut the local
pump off during a DHW heating cycle, but will
keep the local pump on for the
LOCAL
DELAY:
10s
(Programmable) time before
shutting off.
11.
Set the
PURGE TO
value to
TANK
. This will
purge the heat from the boiler into the tank or
system loop. This will be done using the DHW
pump after the DHW heating cycle is complete.
If the
PURGE TO:
is set to
SPACE
, once the DHW
cycle has completed, the boiler will shut the DHW
pump off within a few seconds. The
SPACE
setting is
to be used only for
MIXED
space and DHW heating.
HYB SENSOR = OFF
SETTINGS: DISTRIBUTED CONTROL:
MASTER TYPE
select
AUTO,
DHW
or
COMBINATION
.
JPS1 MUST be cut on all boilers
providing DHW.