MODBUS COMMUNICATIONS
HeatNet Control V3
Page 105
Figure 64
MODBUS Input Variables (Read Only)
Address
Name
Raw Data
Type
Scale
Description
Valid Values/Range
----- The following registers are available starting in firmware version 2.0 -----
30096
Boiler01SupplyTemp
16 bit signed
0.01
Boiler (1
– 16) supply temperature (if
available). See BoilerStatus2 to
determine if the sensor is present.
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
32
– 250 °F
30097
Boiler02SupplyTemp
30098
Boiler03SupplyTemp
30099
Boiler04SupplyTemp
30100
Boiler05SupplyTemp
30101
Boiler06SupplyTemp
30102
Boiler07SupplyTemp
30103
Boiler08SupplyTemp
30104
Boiler09SupplyTemp
30105
Boiler10SupplyTemp
30106
Boiler11SupplyTemp
30107
Boiler12SupplyTemp
30108
Boiler13SupplyTemp
30109
Boiler14SupplyTemp
30110
Boiler15SupplyTemp
30111
Boiler16SupplyTemp
30112
Boiler01ReturnTemp
16 bit signed
0.01
Boiler (1
– 16) return temperature (if
available). See BoilerStatus2 to
determine if the sensor is present.
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
32
– 250 °F
30113
Boiler02ReturnTemp
30114
Boiler03ReturnTemp
30115
Boiler04ReturnTemp
30116
Boiler05ReturnTemp
30117
Boiler06ReturnTemp
30118
Boiler07ReturnTemp
30119
Boiler08ReturnTemp
30120
Boiler09ReturnTemp
30121
Boiler10ReturnTemp
30122
Boiler11ReturnTemp
30123
Boiler12ReturnTemp
30124
Boiler13ReturnTemp
30125
Boiler14ReturnTemp
30126
Boiler15ReturnTemp
30127
Boiler16ReturnTemp
30128
Boiler01CyclesHigh16
16 bit unsigned
---
Boiler (1
– 16) Cycles High (Upper) and
Low (Lower) 16 bit counters. To get the
actual cycle count for any given boiler
(##), the high and low 16 bit counters
must be combined (concatenated) into
a single 32 bit counter as:
Boiler##CyclesHigh16:Boiler##CyclesL
ow16
0
– 4294967295
30129
Boiler01CyclesLow16
30130
Boiler02CyclesHigh16
30131
Boiler02CyclesLow16
30132
Boiler03CyclesHigh16
30133
Boiler03CyclesLow16
30134
Boiler04CyclesHigh16
Summary of Contents for FUTERA XLF Series
Page 27: ...CONTROL METHODS HeatNet Control V3 Page 27 Figure 25 Base loading relay...
Page 67: ...WIRING CONNECTIONS HeatNet Control V3 Page 67 Figure 49 Jumper Dip Switch Locations...
Page 73: ...WIRING CONNECTIONS HeatNet Control V3 Page 73 Figure 57 Temperature sensors...