DHW METHODS
HeatNet Control V3
Page 50
Figure 40
DHW Method 5a
Quick Start
Settings
DHW METHOD 5a: Local Tank Heating Using a DHW Tank Sensor
MASTER
Settings
MASTER Type
HeatNet Address
Combustion Air Damper
Automatic
Automatic
Off
Inputs
Local/Remote
Header Sensor
System Return
Local
Yes
Optional
Outputs
System Pump On
Local Pump On
When Boiler Enabled
When Boiler Running
MEMBER 2
Settings
HeatNet Address
DHW Boiler Mode
DHW Use Sensor
DHW Local Pump Off
Combustion Air Damper
2
Local
Yes
Yes
Off
Inputs
Local/Remote
OR OVR
DHW Sensor
JPS1 Jumper must be cut to service DHW
Remote
Jumper
Yes - Tank #1
Outputs
Local Pump On
DHW Pump On
Space Heating Call
DHW Call
MEMBER 3
Settings
HeatNet Address
DHW Boiler Mode
DHW Use Sensor
DHW Local Pump Off
Combustion Air Damper
3
Local
Yes
Yes
Off
Inputs
Local/Remote
OR OVR
DHW Sensor
JPS1 Jumper must be cut to service DHW
Remote
Jumper
Yes - Tank #2
Outputs
Local Pump On
DHW Pump On
Space Heating Call
DHW Call