DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS
HeatNet Control V3
Page 90
START DAY
MON
Day of the week to begin setback or a day range
TIME
12:00AM
Time to begin setback
END DAY
MON
Day of the week to end the setback or a day range
TIME
12:00AM
Time of the day to end the setback
OPTIONS
TEMP SCALE
F
F or C
Fahrenheit scale is default
KEY CLICK
ON
Beeps when a key is pressed
SKIP PASSWORD
ON
Disables the Password
BRIGHTNESS
50%
25, 50,75,100
Four levels of display brightness, lower for longer life of the display
LOG/RUNTIME
RUN HOURS
Displays runtime hours. Total time the main valve has been open.
DATA LOG ENTRY
Displays the current entry in the data log
SIZE
Displays the current size of the log in entries
BOILER CYCLES
Displays completed boiler cycles. Incremented when the main valve
turns OFF after it has been ON. Does not include attempts to light.
AUX FUNCTIONS
COMBUST AIR
DAMPER
TYPE
LINKED/COMMON
INDEPENDENT
The LINKED/COMMON setting allows one common damper to be
used and controlled by the Master Boiler. All Member boilers must
have their damper prove inputs wired as per
system damper wiring, page 76. Also see Section:
Optional
Features: Auxiliary Function Options
INDEPENDENT: Individual
dampers are in controlled by their respective boiler.
IN USE?
YES
If set to YES, then OUTPUT RELAY K5 can be used to control a
combustion air damper. The Master can control a common system
damper or an individual damper. Members control their respective
damper independent of the Master. Relay K5 is used to enable the
combustion air damper. See
wiring, page 76. Needs to Prove the damper is open.
INPUT:
J12B.7
DAMPER
The damper prove input is dedicated to connect at J12B terminals 7
and 8. If using a common damper refer to the common damper
wiring diagram.
PROOF TIME
2:00
0
– 4min
This is the proving time in minutes for the combustion air damper
prove switch. It is sensed at J12B Pin 7. If the damper faults, a retry
will occur every 10 minutes in attempt to open the damper.
When using J12B in a common damper configuration, wiring is done
beginning with the Master boiler. J12B Pins 7 & 8 are connected to
the prove switch of the combustion damper. Pin 8 is supplying 24
VAC and pin 7 is the sense input. A second wire is connected to
J12B pin 7 of the Master and the other end connected to the first
Member boilers J12B pin 7. If another Member boiler is present,
connect another wire to the J12B Pin 7 terminal of the first Member
and the other end to the second Member boiler J12B pin 7. Continue
this method for each additional boiler.
ALARM SILENCE
ALARM SILENCE IN
USE?
YES
This menu allows the configuration of the Alarm Silence switch. It
can be disabled so that the Alarm Silence switch cannot silence the
alarm until the alarm is cleared; ALARM SILENCE = NO. The
default value is to enable the ALARM SILENCE switch. Holding
down the BACK and SELECT keys at the same time may also be
used to silence the alarm.
INPUT =
J10B STACK
If a stack sensor is used, holding down the BACK and SELECT keys
at the same time is the only way to silence the alarm.