MODBUS COMMUNICATIONS
HeatNet Control V3
Page 101
MODBUS Communications
The Futera III/Fusion-Series control can be controlled using Modbus commands to Enable/Disable the boiler/system. A
connection to the Console Modbus Port on the Communications board is required. The Master Boiler assumes the role of
MEMBER, RTU, 192Kb, 8 bits, Even Parity, 1 stop bit, when connected to a BMS (Building Management System).
The Member Boilers should not be connected to a BMS system other than to view Read Only addresses. Refer to
http://www.rbiwaterheaters.com/
website for greater detail on communicating with Modbus, BACnet, or LonWorks protocols.
Boiler01 = The Modbus connected boiler (Master or Standalone)
Boiler02 = Member 2
Boiler03 = Member 3
…
Boiler16 = Member 16
Figure 63
MODBUS Input/Output Variables (Read/Write)
Address
Name
Raw Data Type
Scale
Description
Valid Values/Range
40001
HeatDemand
1 bit unsigned
---
Heat Demand/Request. Setting the state
Member of this variable will put the boiler
in heating mode.
0 = no heat demand
1 = heat demand
40002
SetpointTimer
16 bit unsigned
---
System Setpoint Timer
The system setpoint timer and system
setpoint work in tandem to externally
control (i.e. a BMS - building management
system) the operating setpoint. The
setpoint (countdown) timer should be
loaded with a timeout value (in seconds)
prior to writing the system setpoint. When
the timer reaches zero, the control assumes
that the BMS is no longer operating and the
local setpoint (saved on the control) is
reloaded. This is a failsafe feature used to
help safeguard the system in case of BMS
failure. If the setpoint timer is not written,
a default timeout value of 60 seconds is
assumed.
0
– 65535 seconds
40003
Setpoint
8 bit unsigned
1.0
System Setpoint (see
SetpointTimer
)
40 - 220 °F
40004
OAResetEnable
1 bit unsigned
---
Enables/Disables outdoor air reset mode.
0 = disabled
1 = enabled
40005
OARSetpoint
8 bit unsigned
1.0
Outdoor air reset setpoint. Temperature at
which boiler shuts down.
40
– 100 °F
40006
OARHighWaterTemp
8 bit unsigned
1.0
Boiler water temperature setpoint when
outdoor air temperature is at the high
outdoor air temperature setpoint
(OARHiAirTemp).
60
– 190 °F
40007
OARHighAirTemp
8 bit unsigned
1.0
High outdoor air temperature setpoint.
50
– 90 °F
40008
OARLowWaterTemp
8 bit unsigned
1.0
Header/Supply temperature setpoint when
outdoor air temperature is at the low
outdoor air temperature setpoint
(OARLoAirTemp).
70
– 220 °F
40009
OARLowAirTemp
8 bit signed
1.0
Low outdoor air temperature setpoint.
-35
– 40 °F
40010
SetMonth
8 bit unsigned
---
Set real time clock – month (
see SetClock
)
0 (January) - 11
(December)
40011
SetDay
8 bit unsigned
---
Set real time clock – day (
see SetClock
)
1
– 31