WR14 / WR50-12/13 Winding Resistance Meter Instruction Manual
Version 3.03
HEAT RUN TEST SOFTWARE
The Heat Run Test Software, option 2042N-11001, is used to analyze the measurement results of the
copper loss test of the windings of a transformer and to calculate the resistance values of the winding at
the working temperature (time zero).
INTRODUCTION
The Heat Run Test (HRT) performs a measurement during the cooling curve of a transformer after the
transformer has been heated.
The measurement is made in the interval
15
mode without temperature correction.
In the Setup Menu the following settings must be made:
Activate “Interval Mode“ and select the interval time.
Select the time in seconds between measuring
points (Interval Time) and the number of data points
(Count).
Disable the Quality Assistant.
The Temperature Correction must be deactivated for
heat run testing.
15
See “Interval” on page 46.