41
•
One illuminators External Input trigger can turn all illuminators in the group
ON (E.g. Car park entrance / Alarm)
•
The Group Override function on the Home Page allows the user to take instant
control of the group of illuminators all at the same time
Group Name
An illuminator can be associated with a new or existing group to enable it to follow
group commands from the photocell input and / or External Input. A new group
name can be created by typing into the
“
Enter Group Name
”
box. Ensure that
duplicate names are avoided. Or the illuminator can be allocated to an existing group
by selecting an existing group from the drop down list of groups.
Trigger Control
For both Photocell and External Input, the user can select 3 action states:
1.
Inactive
T
he illuminator ignores the input
2.
Lamp Control
T
he illuminator will respond to its own input
3.
Group Control
T
he illuminator will respond to an input from illuminators within its
group
–
based on selection from Respond to Group Commands below
Factory Defaults: Photocell
Lamp Control
External Input
Lamp Control
Respond to Group Commands