TO REMOVE/REPLACE THE CENTRAL
HEATING EXPANSION VESSEL
In the unlikely event of failure of the central
heating expansion vessel it is recommended
a suitable expansion vessel be fitted exter-
nal to the boiler. It should be positioned on
the return pipe and as close to the boiler as
possible (Fig. 7).
However, if it is necessary to replace the
central heating expansion vessel the boiler
must be removed from the wall as follows.
Remove the front panel from the outer cas-
ing (sect. 7.3) and lower the instrument
panel (sect. 7.16.2 & 3) and remove the
control box cover (sect. 7.31.213).
Remove the lower grating (sect. 54.2).
Remove the two sides of the casing (sect.
5.4.5).
Close the on/off valve on the domestic cold
water, central heating and gas supply.
Drain domestic water from the lowest hot
water tap and drain point on DHW inlet
cock (Fig. 46).
Drain the boiler (Fig. 93).
Disconnect all pipework connected to boiler.
Disconnect mains cables and any other con-
nections (room thermostat, programming
clock).
Remove the duct proceeding in reverse
order as described in (sect. 5.5 or 5.7).
Remove the 2 lower coach bolts and
release 2 top coach bolts then remove boil-
er from the wall.
7.28.10 Unscrew the nut that connects the expan-
sion vessel and remove it (Fig. 91).
7.28.11 Remove the screw supporting expansion
vessel (Fig. 91).
7.28.12 Remove the expansion vessel.
7.28.13
Replace all the components in reverse order
using new seals.
7.28.14 Fill the system as described in the sect. 6
and check for leaks.
7.29
TO REMOVE/REPLACE THE AIR
AUTOMATIC VENT (Fig. 92)
7.29.1
Remove the front panel from the outer cas-
ing and the combustion chamber front
cover (sect. 7.3 & 4).
7.29.2
Remove the lower grating (sect. 5.4.2)
7.29.3
Remove the fan assembly and the flue
38
Summary of Contents for RSF 82E
Page 39: ...Fig 93 Fig 91...
Page 42: ...SECTION 9 ELECTRICAL SYSTEM DIAGRAM Fig 94...
Page 43: ...44...
Page 44: ...45...
Page 45: ...46...
Page 46: ...SECTlON IO EXPLODED PARTS DIAGRAM...
Page 49: ...NOTES...
Page 50: ...Chartists Way Morley Leeds LS27 9ET Telephone 0113 252 7007 Tfax 0113 238 0229...