background image

Installation Manual 

 

Combi -  cod. 99943NA – November 2002 

 

 

12 

 GAS TYPE CONVERSION 

 

Conversion of the boiler 
from natural gas to LPG 

and vice versa must be 

performed by qualified 

personnel only. 

Conversion is performed 

as follows: 
 

a)  turn off the main power 

switch; 

b)   close the gas cock; 

c)  substitute the jets on 

the main burner as 

follows: 

• 

undo the gas pipe 5 

(fig.1) from the burner 
manifold using a size 

24 spanner; 

• 

separate the burner 

manifold 2 from the 
burner ramps 1 by 

undoing the 4 screws 3 

using a Philips 

screwdriver; 

• 

fit new jets 4 to the 
burner suitable for the 

type of gas the boiler 

will run on using a no. 7 

spanner. The jets must 

be fitted with new 
gaskets; 

• 

reassemble the entire burner unit. Use the soapy water method to check for gas leaks each time gas connections are 

dismantled and reassembled; 

d) change the spring 6 (fig.2) to suit the type of gas used. The spring is located inside the stabiliser in the gas valve 8. To 
change the spring, open the fastening clips 2 and, after unhooking the coil 1, remove the modulator core 7 and change the 

spring; once this has been done reassemble everything; 

e) move the jumper on the circuit board to suit the type of gas (fig.4). 

f) replace the gas setting plate that indicates the type of gas and nominal pressure for the boiler. When converting the boiler to 

work with a different type of gas, remove the existing plate and replace it with the new one supplied in the conversion kit. 

g) calibrate the new max. and min. settings for the modulator. 

  

DATA TABLE 

 

Models: 

RSF 20 E 

 

NATURAL GAS G 20 

LIQUID  BUTAN GAS G  30 

LIQUID PROPANE GAS G 31 

Lower Wobbe index (15°C; 1013 mbar)     

MJ/m3n 

45.67 80.58 

70.69 

Rated feed pressure       

mbar(mm c.w.) 

20(204) 30(306) 

37(377) 

Minimum feed pressure          

mbar(mm c.w.) 

17(173.4) 20(204) 

25(255) 

Main  burner: 13 jets - Ø jet  

mm. 

1.25 0.75 

0.75 

Consuption (15°C; 1013 mbar)                             

mc/h. 

2.8  

 

Consuption (15°C; 1013 mbar)                             

Kg/h. 

 2.10  2.07 

 

Models: 

RSF 24  E 

 

NATURAL GAS G 20 

LIQUID  BUTAN GAS G  30 

LIQUID PROPANE GAS G 31 

Lower Wobbe index (15°C; 1013 mbar)     

MJ/m3n 

45.67 80.58 

70.69 

Rated feed pressure       

mbar(mm c.w.) 

20(204) 30(306) 

37(377) 

Minimum feed pressure          

mbar(mm c.w.) 

17(173.4) 20(204) 

25(255) 

Main  burner: 13 jets - Ø jet  

mm. 

1.25 0.77 

0.77 

Consuption (15°C; 1013 mbar)                             

mc/h. 

3.15  

 

Consuption (15°C; 1013 mbar)                             

Kg/h. 

 2.35  2.32 

 

1

2

3

4

5

11

10

8

7

6

9

4
3

1

11
10

2

5

5

13

12

4

7

5

8

6

1

2

3

LEGEND

1. 

Gas valve mod. VK4105A 

2. 

Pressure modulator 

3. 

Inlet pressure point    

4. 

Outlet pressure point  

5. 

Electronic ignition board 

6. 

Gas pipe 

7. 

Burner manifold 

8. 

13 ramp gas burner 

9. 

Injectors   

10. 

Ignition electrodes 

11. 

Flame ionisation electrodes 

12. 

Ignition board fastening screws 

13. 

Ignition board cover 

 

LEGEND

1. 

Modulating coil 

2. 

Fastening clips 

3. 

Min. gas pressure  adjustament srew 

4. 

Max. gas pressure adjustament core  

5. 

Core lock  nut 

6. 

Calibrator spring (blue natural gas) (grey L.P.G.) 

7. 

Pressure modulator 

8. 

Gas valve stabiliser 

GAS  BURNER UNIT 

PRESSURE  MODULATOR 

Link Jumper on RAMIRE 

ciruit  board

 

Fig. 1 

Fig. 2 

 Fig. 3 

 Fig. 4 

 Fig. 5 

Summary of Contents for RSF 24 E

Page 1: ...LISH Technical Specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY By Technical Department INSTALLATION AND MAINTENANCE MANUAL FOR GAS FIRED WALL HUNG BOILERS Model RSF 20 E RSF 24 E TYPE C R...

Page 2: ......

Page 3: ...4 BOILER INSTALLATION page 6 ELECTRICAL CONNECTIONS page 8 16 17 BOILER CONTROL PANEL page 8 STARTING UP THE BOILER FOR THE FIRST TIME page 9 BOILER ADJUSTMENTS page 11 GAS TYPE CONVERSION page 12 REG...

Page 4: ...expansion vessel 2 WARNINGS REGARDING INSTALLATION Warranty expires 12 months from date of installation and in all cases no later than 18 months from date of construction First start up must be perfor...

Page 5: ...w 11 15 BTU h 37498 51187 Heating temperature adjustment C 30 80 30 80 Max working pressure heating bar 3 3 Min working pressure heating bar 0 3 0 3 Expansion vessel capacity initial pressure 1 bar Li...

Page 6: ...aust into a flue duct and the air intake directly from an external wall To insert a bend reduce total flue length by 1 5 m R RETURN G GAS C HOT WATER F COLD WATER A HEATING FLOW NOTE USE ORIGINAL RADI...

Page 7: ...8 Pipework that supplies the boiler must be a 22 mm ininterrupted supply from meter to the isolation cock of the boiler The complete installation must be tested for soundness as described in the above...

Page 8: ...d Where the lowest part of the terminal is fitted less than 2m 6 6ft above a balcony above ground or above a flat roof to which people have access the terminal MUST be protected by a purpose designed...

Page 9: ...d to the heating system with the fittings supplied with the boiler JIG Connect pipes and valves as shown in the picture 5 Position the boiler paying attention to hang it to the hanging bracket do not...

Page 10: ...or and 4 C Hot water sensor and protects the boiler down to 2 C external temperature To protect the internal Radiators a room thermostat or remote control must be fitted NOTE The frost system will onl...

Page 11: ...nd open the electrical control box by lifting the cover as shown in fig 1 E With the electrical control box now open make the following connections Connect the yellow green wire to the terminal marked...

Page 12: ...eaks The checking procedure for the gas burner attachment is carried out with the boiler working make sure the electrical mains switch is OFF remove the front cover by pulling it forwards undo the sid...

Page 13: ...pressure is equal to that stated on the plate to check the minimum undo one wire from the modulator coil and check on the gauge that the minimum pressure is equal to that stated on the plate if the m...

Page 14: ...ll screwdriver for any adjustments Turn clockwise to increase gas pressure to the burner at start up by setting the trimmer to maximum calibration pressure of modulator see page 16 Turn counter clockw...

Page 15: ...replace it with the new one supplied in the conversion kit g calibrate the new max and min settings for the modulator DATA TABLE Models RSF 20 E NATURAL GAS G 20 LIQUID BUTAN GAS G 30 LIQUID PROPANE...

Page 16: ...de out the coil 1 located above the gas valve Fig D Tighten plastic screw 3 by turning it clockwise be careful not to break it Fig E Use a no 17 spanner to undo the lock nut 5 which holds the core 4 o...

Page 17: ...lve body following instructions from no 1 to no 4 see fig 1 To separate the motor from the valve body proceed as follows 1 Press button A under the motor 2 Simultaneously keep the A button pressed and...

Page 18: ...N CHAMBER 4 ROOM SEALED CHAMBER COVER 5 ROOM SEALED CHAMBER BACK 6 HEAT EXCHANGER Mod 20 000 HEAT EXCHANGER Mod 24 000 7 D H W EXCHANGER H20 H20 PB 21 73 D H W EXCHANGER H20 H20 PB 24 73 8 EXCHANGER A...

Page 19: ...C6 C7 RS1 R58 R22 R21 4 2 1 3 15 14 22 LED2 LED1 LED3 LED4 RAVI II R31 42 R18 R17 yellow blue R48 FA1 C20 R49 R23 R24 R47 C19 C21 red brown R39 C9 M9 R62 R61 R57 J16 R38 C5 J20 R37 41 R16 C14 IC2 J7...

Page 20: ...24 18 22 12 13 12 11 EA 8 ER 6 RPA P 15 PTC2 14 5 20 21 V RVA 16 2 1 3 7 4 PA VD NET FILTER IG R CY CY CX N L AIR PRESSURE SWITCH FAN PUMP RELAY CONTACT D H WATER RELAY CONTACT FAN RELAY CONTACT THER...

Page 21: ...e When dismantling the boiler casing be careful when removing the side panels after having removed the front panel the front panel is removed by undoing the lower and front fixing screws and then remo...

Page 22: ...lace it d change over polarity e make earth connection f fit conversion kit 4 Boiler on temperature rises rapidly and extinguishes flame light 2 fig 1 on a circulation pump burned out or blocked b air...

Page 23: ...24028LA CIRCULATING PUMP MOTOR 9 9 13 96008LA 3 BAR PRESSURE RELIEF VALVE 1 2 9 9 14 59010LA WATER PRESSURE SWITCH 1 8 9 9 15 96030LA AUTOMATIC AIR VENT VALVE 5020 3 8 9 9 16 95011LA 8 LT EXPANSION TA...

Page 24: ...s and illustrations contained in this leaflet have been carefully prepared but we reserve the right to make changes and improvements in our products whitch may affect the accurancy of the information...

Reviews: