background image

Installation Manual 

 

Combi -  cod. 99943NA – November 2002 

 

 

TA

OR

TA

N

L

ye

llo

w

red

5 4

bl

ue

3

2

br

own

1

OR

TA

M

N

L

PT

OR

ye

llo

w

TA

PT

red

5 4

N

L

bl

ue

3

2

br

own

1

OR

TA

TA

PT

M

N

L

BROWN

GIALLO/VERDE

LIGHT BLUE

BLACK

LIGHT BLUE

BLACK

BLACK

BROWN

YELLOW/GREEN

1

2

VT

ELECTRICAL CONNECTIONS  

 

The boiler works with 230 V 50 Hz AC current 

and has maximum input of 170 W. Connection 
to the electrical mains must be performed with 
a device having an omnipolar opening of at 

least 3 mm. Make sure the live and neutral 
connections conform to the diagram. 

A secure 

earth connection is compulsory.

 

 

IMPORTANT

 

 
If you need to replace the power supply cable, 
use cable having the same characteristics: 

(HO5 W-F) 3x1 with maximum external 
diameter 8 mm.). Connect to the terminal block 

located in the instrument panel as follows: 
 
A.  Turn off the electrical power supply at the 

mains. 

B.   Remove the boiler front casing. 
C.  Undo the two side screws on the panel 

using the phillips screwdriver VT and turn it 
to the position shown in fig.1 (pos. 1). 

D.  After pulling the panel downwards, undo 

the four rear screws on the housing and 
open the electrical control box by lifting the 

cover as shown in fig.1. 

E.  With the electrical control box now open 

make the following connections: 

• 

Connect the yellow/green wire to the 
terminal  marked  with  the  earth  symbol        
“   “  (see fig.1). 

• 

Connect the blue wire to the terminal 

marked with the letter “N”. 

• 

Connect the brown wire to the terminal 
marked with the letter “L”. 

 
 

CONNECTION OF ROOM THERMOSTAT 

 

NOTE

: use low voltage

 

room thermostats only.   

 

The thermostat wire must not be placed in the 
channel containing high tension wires, but must 

have its own line  
The room thermostat lead must not exceed 
50m n length; minimum section 0.5 mm.  

 

Connection

: after carrying out the operations 

described on page 15, proceed as follows: 

A.   Insert the room thermostat lead into the 

entry point on the electrical control box 
along with all the other leads on the 

boiler. 

B.   Move the bridge 

PT

 (see fig.1)  from 

terminal 

TA

 to the free one next to it. 

C.   Insert the thermostat wires (fig.2) one in 

terminal 

TA

 and the other in the one next 

to it occupied by bridge 

PT

 which you 

have just moved. 

 

If a timer is fitted as well as a room thermostat, carry out the electrical connections for the timer according to the indications in figures 3 (tipe 
clock + room thermostat) and 4 (time clock only). 

Fig. 1 

Fig. 5 

Fig. 4 

Fig. 2 

Fig. 7 

Fig. 6 

Fig. 3 

Summary of Contents for RSF 24 E

Page 1: ...LISH Technical Specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY By Technical Department INSTALLATION AND MAINTENANCE MANUAL FOR GAS FIRED WALL HUNG BOILERS Model RSF 20 E RSF 24 E TYPE C R...

Page 2: ......

Page 3: ...4 BOILER INSTALLATION page 6 ELECTRICAL CONNECTIONS page 8 16 17 BOILER CONTROL PANEL page 8 STARTING UP THE BOILER FOR THE FIRST TIME page 9 BOILER ADJUSTMENTS page 11 GAS TYPE CONVERSION page 12 REG...

Page 4: ...expansion vessel 2 WARNINGS REGARDING INSTALLATION Warranty expires 12 months from date of installation and in all cases no later than 18 months from date of construction First start up must be perfor...

Page 5: ...w 11 15 BTU h 37498 51187 Heating temperature adjustment C 30 80 30 80 Max working pressure heating bar 3 3 Min working pressure heating bar 0 3 0 3 Expansion vessel capacity initial pressure 1 bar Li...

Page 6: ...aust into a flue duct and the air intake directly from an external wall To insert a bend reduce total flue length by 1 5 m R RETURN G GAS C HOT WATER F COLD WATER A HEATING FLOW NOTE USE ORIGINAL RADI...

Page 7: ...8 Pipework that supplies the boiler must be a 22 mm ininterrupted supply from meter to the isolation cock of the boiler The complete installation must be tested for soundness as described in the above...

Page 8: ...d Where the lowest part of the terminal is fitted less than 2m 6 6ft above a balcony above ground or above a flat roof to which people have access the terminal MUST be protected by a purpose designed...

Page 9: ...d to the heating system with the fittings supplied with the boiler JIG Connect pipes and valves as shown in the picture 5 Position the boiler paying attention to hang it to the hanging bracket do not...

Page 10: ...or and 4 C Hot water sensor and protects the boiler down to 2 C external temperature To protect the internal Radiators a room thermostat or remote control must be fitted NOTE The frost system will onl...

Page 11: ...nd open the electrical control box by lifting the cover as shown in fig 1 E With the electrical control box now open make the following connections Connect the yellow green wire to the terminal marked...

Page 12: ...eaks The checking procedure for the gas burner attachment is carried out with the boiler working make sure the electrical mains switch is OFF remove the front cover by pulling it forwards undo the sid...

Page 13: ...pressure is equal to that stated on the plate to check the minimum undo one wire from the modulator coil and check on the gauge that the minimum pressure is equal to that stated on the plate if the m...

Page 14: ...ll screwdriver for any adjustments Turn clockwise to increase gas pressure to the burner at start up by setting the trimmer to maximum calibration pressure of modulator see page 16 Turn counter clockw...

Page 15: ...replace it with the new one supplied in the conversion kit g calibrate the new max and min settings for the modulator DATA TABLE Models RSF 20 E NATURAL GAS G 20 LIQUID BUTAN GAS G 30 LIQUID PROPANE...

Page 16: ...de out the coil 1 located above the gas valve Fig D Tighten plastic screw 3 by turning it clockwise be careful not to break it Fig E Use a no 17 spanner to undo the lock nut 5 which holds the core 4 o...

Page 17: ...lve body following instructions from no 1 to no 4 see fig 1 To separate the motor from the valve body proceed as follows 1 Press button A under the motor 2 Simultaneously keep the A button pressed and...

Page 18: ...N CHAMBER 4 ROOM SEALED CHAMBER COVER 5 ROOM SEALED CHAMBER BACK 6 HEAT EXCHANGER Mod 20 000 HEAT EXCHANGER Mod 24 000 7 D H W EXCHANGER H20 H20 PB 21 73 D H W EXCHANGER H20 H20 PB 24 73 8 EXCHANGER A...

Page 19: ...C6 C7 RS1 R58 R22 R21 4 2 1 3 15 14 22 LED2 LED1 LED3 LED4 RAVI II R31 42 R18 R17 yellow blue R48 FA1 C20 R49 R23 R24 R47 C19 C21 red brown R39 C9 M9 R62 R61 R57 J16 R38 C5 J20 R37 41 R16 C14 IC2 J7...

Page 20: ...24 18 22 12 13 12 11 EA 8 ER 6 RPA P 15 PTC2 14 5 20 21 V RVA 16 2 1 3 7 4 PA VD NET FILTER IG R CY CY CX N L AIR PRESSURE SWITCH FAN PUMP RELAY CONTACT D H WATER RELAY CONTACT FAN RELAY CONTACT THER...

Page 21: ...e When dismantling the boiler casing be careful when removing the side panels after having removed the front panel the front panel is removed by undoing the lower and front fixing screws and then remo...

Page 22: ...lace it d change over polarity e make earth connection f fit conversion kit 4 Boiler on temperature rises rapidly and extinguishes flame light 2 fig 1 on a circulation pump burned out or blocked b air...

Page 23: ...24028LA CIRCULATING PUMP MOTOR 9 9 13 96008LA 3 BAR PRESSURE RELIEF VALVE 1 2 9 9 14 59010LA WATER PRESSURE SWITCH 1 8 9 9 15 96030LA AUTOMATIC AIR VENT VALVE 5020 3 8 9 9 16 95011LA 8 LT EXPANSION TA...

Page 24: ...s and illustrations contained in this leaflet have been carefully prepared but we reserve the right to make changes and improvements in our products whitch may affect the accurancy of the information...

Reviews: