INSTALLATION INSTRUCTIONS
RK 100 - RAD - ING - MAN.INST - 1311.1 - DIGITECH CS MIAH4
31
3.9.3.2
Flue type
KIT FK 100 – cod. 82280LP
Vertical flue kit Ø100 mm in polypropylene
.
Discharges exhaust fumes and draws air directly from high Level.
Ø100
80
0
MAXIMUM FLUE LENGTH
The maximum flue length (linear equivalent) is obtained:
a.
Through the sum of individual components flue lengths (linear equivalent) that must be lower than 15 m;
N.B. A 30 mt maximum flue length can be reached by setting the parameters’ value to 180 Hz. Operate
according to the instructions of “5.3 Setting the parameters” to modify the parameters’ value.
b.
Through the sum of individual components’ flue efficiency losses, that must be lower than 146 Pa.
The maximum flue length can be obtained according to the following table:
Description
Equivalent lenght
m
Flue efficiency loss
Pa
Extension Ø100 L = 1000 mm MF polypropylene
1
5.8
Vertical connector Ø100 w/test point MF polypropylene
0.5
2.9
90° Flue bend Ø100 MF polypropylene
3
17.5
45° Flue bend Ø100 MF polypropylene
1.4
7.8
Fig. 1