TECHNICAL CHARACTERISTICS
RK 100 - RAD - ING - MAN.INST - 1311.1 - DIGITECH CS MIAH4
5
Gas Supply
Natural Gas G20
Nominal inlet pressure
mbar
20
Nominal inlet pressure – max
mbar
23
Nominal inlet pressure – min
mbar
15
Gas consumption
m
3
/h 10.42
Electrical specifications
Power supply
V/Hz
230/50
Electrical power consumption
W
430
Pump electrical power consumption
W
240
Electrical power consumption – boiler OFF
W
5.4
Electrical protection
IP
X4D
Combustion Data
Combustion Efficiency – (100% full load)
%
97.6
Combustion Efficiency – (minimum load)
%
98.2
Flue efficiency losses with burner ON (100% full load)
%
2.4
Flue Efficiency losses with burner ON (minimum load)
%
1.8
Casing Efficiency losses (100% full load)
%
0.1
Casing Efficiency losses (minimum load)
%
1
Flue Efficiency losses with burner OFF
%
0.02
Casing Efficiency losses with burner OFF
%
0.03
Flue gas temperature – Heat Input max
°C
74.6
Flue gas temperature – Heat Input min
°C
61.2
Flue Mass at Heat Input max (80/60°C)
kg/h
159.6
Flue Mass at Heat Input min (80/60°C)
kg/h
40
CO
2
value at Heat Input max
%
9.4
CO
2
value at Heat Input min
%
9.2
CO value at Heat Input max (0% O
2
) Weighted
ppm
10
CO value at Heat Input min (0% O
2
) ppm
5
NOx ppm
13
NOx mg/kWh
23
NOx Emissions (UNI EN 297)
Class
5