REGULATION INSTRUCTIONS
RK 100 - RAD - ING - MAN.INST - 1311.1 - DIGITECH CS MIAH4
44
PARAMETER
P09
–
D.H.W/STORAGE
CYLINDER
PUMP
OVERRUN
TIMER
N.B. RS version only - with connection to a remote storage cylinder
This parameter is used to set the pump functioning time, in D.H.W mode,
after closing the water tap.
To enter the parameters menu, follow the previously described procedure
(
see paragraph
5.2 ‘Accessing the parameters menu’
- steps 1-4).
5.
Use ‘
’ and ‘
’ buttons
S
symbol side
to modify the value of
the parameter within the prescribed limits (displayed in multiples of 5
seconds):
min = 00
max = 90
For ex.: 90 = 90 x 5” = 450” (7,5 min)
The default value is 18 = 90” = 1.5 min
6.
Press mode selection button ‘
’ to confirm and to render the new
parameter operative.
7.
To exit from the parameters menu, press simultaneously ‘
’ and
‘
’ buttons.
PARAMETER
P10
–
SETS
THE
MINIMUM
FAN
SPEED
This parameter is used to set the minimum fan speed which corresponds
to the minimum burner output.
To enter the parameters menu, follow the previously described procedure
(
see paragraph
5.2 ‘Accessing the parameters menu’
- steps 1-4).
5.
Use ‘
’ and ‘
’ buttons
S
symbol side
to modify the value of
the parameter within the prescribed limits (displayed in Hertz):
min = 33 Hz
max = Value set in parameter P11
The default value is set according to the output value set in Parameter
P00.
6.
Press mode selection button ‘
’ to confirm and to render the new
parameter operative.
7.
To exit from the parameters menu, press simultaneously ‘
’ and
‘
’ buttons.
PARAMETER
P11
–
SETS
THE
MAXIMUM
FAN
SPEED
This parameter is used to set the maximum fan speed which corresponds
to the maximum burner output.
To enter the parameters menu, follow the previously described procedure
(
see paragraph
5.2 ‘Accessing the parameters menu’
- steps 1-4).
5.
Use ‘
’ and ‘
’ buttons
S
symbol side
to modify the value of
the parameter within the prescribed limits (displayed in Hertz):
min = Value set in parameter P10
max = 203 Hz
The default value is set according to the output value set in Parameter
P00.
6.
Press mode selection button ‘
’ to confirm and to render the new
parameter operative.
7.
To exit from the parameters menu, press simultaneously ‘
’ and
‘
’ buttons.
P11
P11
170
P10
61
P10
60
18
P09
36
P09
S
S
S
S
S
S
171