REGULATION INSTRUCTIONS
RK 100 - RAD - ING - MAN.INST - 1311.1 - DIGITECH CS MIAH4
47
PARAMETER
P17
–
SETS
THE
TEMPERATURE
MEASUREMENT
UNIT
This parameter is used to set the temperature measurement unit
displayed: Celsius (
) or Fahrenheit ( ) degrees.
To enter the parameters menu, follow the previously described
procedure (
see paragraph
5.2 ‘Accessing the parameters menu’
- steps
1-4).
5.
Use ‘
’ and ‘
’ buttons
S
symbol side
to modify the value of
the parameter:
00 = °C
01 = °F
6.
Press mode selection button ‘
’ to confirm and to render the
new parameter operative.
7.
To exit from the parameters menu, press simultaneously ‘
’ and
‘
’ buttons.
PARAMETER
P18
–
SETS
THE
0-10V
INDUSTRIAL
BUS
PILOTING
This parameter is used to enable/disable the 0-10V industrial bus in
order to set the burner output and the flow temperature by outdoor bus.
To enter the parameters menu, follow the previously described
procedure (
see paragraph
5.2 ‘Accessing the parameters menu’
- steps
1-4).
5.
Use ‘
’ and ‘
’ buttons
S
symbol side
to modify the value of
the parameter:
00 = Disabled
01 = Flow temperature control mode
02 = Burner output control mode
6.
Press mode selection button ‘
’ to confirm and to render the
new parameter operative.
7.
To exit from the parameters menu, press simultaneously ‘
’ and
‘
’ buttons.
PARAMETER
P19
–
CENTRAL
HEATING
MINIMUM
SET
POINT
This parameter is used to set the central heating minimum user set
point.
To enter the parameters menu, follow the previously described
procedure (
see paragraph
5.2 ‘Accessing the parameters menu’
- steps
1-4).
5.
Use ‘
’ and ‘
’ buttons
S
symbol side
to modify the value of
the parameter within the prescribed limits (displayed in Celsius
degrees):
min = 20 °C
max = 40 °C
6.
Press mode selection button ‘
’ to confirm and to render the
new parameter operative.
7.
To exit from the parameters menu, press simultaneously ‘
’ and
‘
’ buttons.
P19
35
P19
30
P18
02