INSTALLATION INSTRUCTIONS
RK 100 - RAD - ING - MAN.INST - 1311.1 - DIGITECH CS MIAH4
26
Ta
B
LN
Ta
Se
Se
A
TA
CR
SE
Fig. 1
3.8.3 Electrical connections (Option)
Remote control connection – cod. 40-00017
Outdoor temperature sensor cod. 73518LA
3.8.3.1 Remote control (option) connection
Connect the wires to the terminal board inside the instrument panel as follows:
a.
switch off the power supply at the main switch.
b.
remove the front case panel of the boiler.
c.
slacken the screws and remove plate
A
(see fig. 1).
d.
remove jumper TA -TA from the terminal board
B
;
e.
connect the remote control wires on contacts marked as TA-TA;
3.8.3.2 Outside temperature sensor connection (Option)
Connect the wires to the terminal board inside the instrument panel as follows:
a.
switch off the power supply at the main switch.
b.
remove the front case panel of the boiler.
c.
slacken the screws and remove plate
A
(see fig. 1).
d.
connect the outside temperature sensor on contacts marked as SE-SE on the terminal board
B
;
When the wires have been connected, place plate “
A
" back to position and then the front case panel.
Note: in the case of simultaneous presence of outdoor temperature sensor and remote control, the electronic
board only sends the value of outdoor temperature to the remote device without using it for the modulation. The
remote device will use the value for modulation, if necessary. (See the manual of the remote).
The communication between the electronic board and the remote control takes place regardless of the mode of
operation selection made in the boiler, and once the connection is established, the onboard user interface is
disabled and the display will show the symbol
'
Key
SE
Outdoor temperature
sensor
TA
Room thermostat
CR
Open Therm Remote
control (cod. 40-00017)