35
Rada Pulse Relay Box (accessory)
The auxiliary channels of the rada pulse control box must be programmed if a
rada pulse relay box has been installed. refer to the rada pulse hand held
programmer product manual.
Final Commissioning - Walk Test
for
Pulse Ceiling sensors 124, 125
and
126
, operate the sensor by body movement
within the sensor target area (for adjustment refer to section:
'2. Install the sensors,
2.3 Rada Pulse 124, 125 and 126 Ceiling sensors'
).
for
Pulse 124 Washbasin sensor
operate the sensor by hand movement. The
target area should be adjusted to the front central area of the washbasin.
for
Pulse 125 single Urinal,
or
Pulse 126 Group Urinal
, the target area should
be aimed and adjusted appropriate to use.
for
Pulse 120, 129
and
lR sensors
operate the sensor by hand movement close
to the front of the sensor lens.
for
Pulse 122 sensor
, operate the sensor using body movement within 550 mm
of the front of the sensor lens.
check each pulse sensor within the installation. make sure that the pulse washroom
system provides the required output when each sensor is triggered and that the
water flow is not initiated by passers-by outside the Sensor detection area.
It may be necessary to turn on the water supply to check that water can flow in
response to sensor activation.
Warning! Additional testing must be carried out if hot water disinfection has
been installed to make sure that hot water cannot accidentally be discharged
onto persons who may be present within a showering or washbasin facility.
Particular care must be taken during installation to make sure that the hot
water disinfection system cannot be accidentally triggered. An effective
interlock system is required. The disinfection system must only be operated
by designated and trained persons (Refer to the Rada Pulse Hand Held
Programmer Product Manual for programming instructions).
always observe safety precautions. Test the complete washroom system to check
that all pulse sensors, Valves and auxiliaries are programmed and operating to