COMMIssIONING / PROGRAMMING
The rada pulse hand held programmer is required to commission the control box
for use with the pulse washroom system. The programmer package contains a
written manual with programming details for the rada pulse washroom system.
Installation Check
when the installation of the rada pulse system is complete, the installer should check
that all pulse sensors, solenoid Valve/s and other system components (Keyswitch,
auxiliaries etc) are connected to the appropriate terminals in the rada pulse control
box. isolate the water supply to the system and switch on the electric supply.
if the rada pulse hand held programmer is not available the sensor function can be
checked at the control box sensor terminal screws by using a dVm voltmeter. when
a connected pulse sensor is activated the measured voltage should momentarily
reduce and then return back to 12V ac ± 1V.
Commission the system
commissioning must be carried out in accordance with these instructions and must
be conducted by designated, qualified and competent personnel.
refer to the rada pulse hand held programmer product manual 'operation, program
a channel' for full commissioning instructions.
remove the threaded plug at the top of the control box and, with the arrow facing
forward, plug the hand held programmer into the mating socket. by accessing the
programmer menu: 'system info channel' a check can be made to determine if
sensors are active (sensor triggered) or inactive (sensor not triggered). The sensor
input channels must be programmed before the system info channel menu can be
used in this way.
each rada pulse sensor input channel will be at the default setting 'shower on for
30 seconds' when mains power is connected to the rada pulse control box for the
first time. The Hand Held Programmer must be used to program each connected
sensor input of the rada pulse control box to the required system function (shower,
urinal, wc, washbasin). unused (unconnected) sensor input channels of the rada
pulse control box do not require programming and must be left at the default setting