SECTION 9 – SERVICE AND TROUBLESHOOTING
9
TABLE 33 -
PRESSURE TRANSDUCERS
0-400 PSIG SUCTION
PRESSURE
TRANSDUCER
0-600 PSIG DISCHARGE
PRESSURE
TRANSDUCER
PRESSURE
PSIG
VOLTAGE
VDC
PRESSURE
PSIG
VOLTAGE
VDC
0
0.5
0
0.5
50
1.0
75
1.0
100
1.5
150
1.5
150
2.0
225
2.0
200
2.5
300
2.5
250
3.0
375
3.0
300
3.5
450
3.5
350
4.0
525
4.0
400
4.5
600
4.5
RED WIRE = 5V, BLACK WIRE = 0V, WHITE/GREEN WIRE = SIGNAL
TEST POINTS:
Suction Pressure:
System 1: ...............................................Microboard J7-10 to J7-9
System 2: ...............................................Microboard J9-10 to J9-9
Discharge Pressure:
System 1: ...............................................Microboard J7-11 to J7-7
System 2: ...............................................Microboard J9-11 to J9-7
V = (Pressure in psig x .01) + .5
or
V = (Pressure in barg x .145) + .5
where V = DC voltage output
Pressure = pressure sensed by transducer
The I/O board connections for the Discharge
Transducers are as follows.
System 1 Discharge Transducer
J7-6 = +5 VDC regulated supply to transducer.
J7-11 = VDC input signal to the microboard. See the
formula above for voltage readings that cor-
respond to specific discharge pressures.
J7-7 = +5 VDC return
J7-2 = drain (shield connection = 0 VDC)
System 2 Discharge Transducer
J9-6 = +5 VDC regulated supply to transducer.
J9-11 = VDC input signal to the microboard.
S
ee the
formula above for voltage readings that correspond to
specific discharge pressures.
J9-7 = +5 VDC return
J9-2 = drain (shield connection = 0 VDC)
The suction transducers have a range from 0 psig to
400 psig (27.5 barg). The output will be linear from 0.5
VDC to 4.5 VDC over the 400 psig (27.5 barg) range.
Following is a formula that can be used to verify the
voltage output of the transducer. All voltage reading
are in reference to ground (unit case).
V = (Pressure in psig x .02) + .5
or
V = (Pressure in barg x .29) + .5
where V = DC voltage input to microprocessor
Pressure = pressure sensed by transducer
Following are the I/O board connections for the Suc-
tion Transducer.
System 1 Suction Transducer
J7-5 = +5 VDC regulated supply to transducer.
J7-10 = VDC input signal to the microboard. See the
formula above for voltage readings that cor-
respond to specific suction pressures.
J7-9 = +5 VDC return.
J7-1 = drain (shield connection = 0VDC).
System 2 Suction Transducer
J9-5 = +5 VDC regulated supply to transducer.
J9-10 = VDC input signal to the microboard. See the
formula above for voltage readings that
correspond to specific suction pressures.
J7-9 = +5 VDC return.
J7-11 = drain (shield connection = 0VDC).
Digital Outputs
See the unit wiring diagram and
. The digital outputs are located on TB7, TB8, and
TB9 and TB-10 of the microboard. All outputs are 120
VAC with the exception of TB8-6 to TB8-7 which are
the contacts that can be used for a remote evaporator
pump start signal. The voltage applied to either of these
terminals would be determined by field wiring.
Summary of Contents for QTC3040T
Page 10: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 34: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 73: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 110: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 168: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...