179
QUANTECH
FORM QTC3-NM1
ISSUE DATE 08/03/2022
SECTION 9 – SERVICE AND TROUBLESHOOTING
9
OPTIONAL PRINTER INSTALLATION
The micro panel is capable of supplying a printout
of chiller conditions or fault shutdown information at
any given time. This allows operator and service per-
sonnel to obtain data and system status with the touch
of the keypad. In addition to manual print selection,
the micro panel will provide an automatic printout
whenever a fault occurs. Detailed explanation of the
print function is given under
.
Parts
The following parts are required:
1. Printer.
2. Desk top calculator paper, 2.25 in. (5.7 cm) wide.
3. Twisted Pair Shielded Cable (minimum 3 conduc-
tor), #18 AWG stranded, 300 V minimum insula-
tion, 25 ft (7.62 m) maximum length.
4. One 25 pin Cannon connector and shell.
5. Cannon P/N DB-25P connector, or equivalent.
6. Cannon P/N DB-C2-J9 shell.
Assembly and Wiring
All components should be assembled and wired as
shown in Figure 35. Strip the outside insulation back
several inches and individual wires about 3/8” (9.5
mm) to connect the cable at the Microboard. Do not
connect the shield at the printer-end of the cable.
Obtaining a Printout
A printout is obtained by pressing the PRINT key on
the keypad and then pressing either the OPER DATA
key or HISTORY key.
TABLE 34 -
DATA LOGGING TO FLASH (CONT’D)
DATA
NUMBER
HEADER
DATA
TEXT
UNIT
FORMAT
VALUE DESCRIPTION
75
S1 Prop Cont In
x
Sys 1 CSHALG_PROPORTIONAL_CONTRIBUTION_INDEX
(0-10000 in x100 format)
76
S1 Int Cont In
x
Sys 1 CSHALG_INTEGRAL_CONTRIBUTION_INDEX
(0-1000000 in x10000 format)
77
S1 Der Cont In
x
Sys 1 CSHALG_DERIVATIVE_CONTRIBUTION_INDEX
(0-10000 in x100 format)
78
S2 Full PID Index
x
Sys 2 CSHALG_FULL_PID_ACTIVE_INDEX
(0 = Disable, 1 = Active)
79
S2 Dim PID Index
x
Sys 2 CSHALG_DIMINISHED_PID_ACTIVE_INDEX
(0 = Disable, 1 = Active)
80
S2 Alg Ctrl Act
x
Sys 2 CSHALG_ALGORITHM_CONTROL_ACTIVE
(0 = Disable, 1 = Enable)
81
S2 Sheat Ex In
x
Sys 2 CSHALG_SUPERHEAT_EXCURSIONS_INDEX
(0 – 255 in x1 format)
82
S2 Prop Cont In
x
Sys 2 CSHALG_PROPORTIONAL_CONTRIBUTION_INDEX
(0-10000 in x100 format)
83
S2 Int Cont In
x
Sys 2 CSHALG_INTEGRAL_CONTRIBUTION_INDEX
(0-1000000 in x10000 format)
84
S2 Der Cont In
x
Sys 2 CSHALG_DERIVATIVE_CONTRIBUTION_INDEX
(0-10000 in x100 format)
85
S1 Thr Limit
%
x
Sys 1 CSHALG_EEV_THROTTLE_LIMIT (0-10000 in x100 format)
86
S2 Thr Limit
%
x
Sys 2 CSHALG_EEV_THROTTLE_LIMIT (0-10000 in x100 format)
Summary of Contents for QTC3040T
Page 10: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 34: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 73: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 110: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 168: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...