181
QUANTECH
FORM QTC3-NM1
ISSUE DATE 08/03/2022
SECTION 9 – SERVICE AND TROUBLESHOOTING
9
TROUBLESHOOTING
TABLE 35 -
TROUBLESHOOTING
PROBLEM
CAUSE
SOLUTION
NO DISPLAY ON PANEL. UNIT
WILL NOT OPERATE
1. No 115 VAC to 24 VAC
Transformer.
1a. Check wiring and fuse 1FU.
1b. Check wiring emergency stop contacts 5 to
L of XTBC2 Terminal Block.
1c. Replace Control Transformer.
2. No 24 VAC to Microboard.
2. Check wiring Control Transformer to
Microboard.
3. Control Transformer defective,
no 24 VAC output.
3. Replace Control Transformer.
4. Short in wire to temp. sensors or
pressure transducers.
4. Unplug connections at IPU II & I/O Board to
isolate.
5. Defective IPU II & I/O Board or
the Display Board.
5. Replace IPU II & I/O Board or the Display
Board.
Contact Quantech Service be-
fore replacing circuit Boards!
FLOW SWITCH/REM STOP NO
RUN PERMISSIVE
1. No chilled liquid flow.
1. Check chilled liquid flow.
2. Flow switch improperly installed.
2. Check that the flow switch is installed
according to manufacturer’s instructions.
3. Defective flow switch.
3. Replace flow switch.
4. Remote cycling device open.
4. Check cycling devices connected to
terminals 13 and 14 of the XTBC1 Terminal
Block.
LOW SUCTION PRESSURE
FAULT
1. Improper suction pressure
cutouts adjustments.
1. Adjust per recommended settings.
2. Low refrigerant charge.
2. Repair leak if necessary and add refrigerant.
3. Fouled filter dryer.
3. Change dryer/core.
4. TXV defective.
4. Replace TXV.
5. Reduced flow of chilled liquid
through the cooler.
). Check operation
of pump, clean pump strainer, purge chilled
liquid system of air.
6. Defective suction pressure
transducer/low pressure switch
or wiring.
6. Replace transducer/low pressure switch or
pressure/voltage formula.
7. LLSV defective
7. Replace LLSV
HIGH DISCHARGE PRESSURE
FAULT
1. Condenser fans not operating or
operating backwards.
1. Check fan motor, and contactors. Assure fan
blows air upward.
2. Too much refrigerant.
2. Remove refrigerant.
3. Air in refrigerant system.
3. Evacuate and recharge system.
4. Defective discharge pressure
transducer.
4. Replace discharge pressure transducer.
for pressure/voltage
formula.
Summary of Contents for QTC3040T
Page 10: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 34: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 73: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 110: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 168: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...