QUANTECH
108
FORM QTC3-NM1
ISSUE DATE 08/03/2022
SECTION 6 – COMMISSIONING
SETPOINTS ENTRY LIST
UNIT OPTIONS
Display Language
System 1 Switch
System 2 Switch
Chilled Liquid
Ambient Control*
Local/Remote Mode
Control Mode
Display Units
Lead/Lag Control*
Fan Control*
Manual Override
Power Fail Restart
Soft Start**
Unit Type**
Refrigerant Type**
Flash Card Update
Remote Temperature Reset
External Evaporator Pump
YORK Hydro Kit Pump
Pump Selection
Data Log to Flashcard Enabled
Expansion Valve Type**
COOLING SETPOINTS
Cooling Setpoint
Range
EMS-PWM Max. Setpoint
PROGRAM SETPOINTS
Discharge Pressure Cutout
Suction Pressure Cutout
Low Ambient Temp. Cutout
Leaving Liquid Temp. Cutout
Anti-Recycle Time
Fan Control ON Pressure
Fan Differential OFF Pressure
Total # of Compressors
Number of Fans/System*
Unit/System Voltage*
Remote Unit ID
* Not on All Models **Viewable Only
F. STARTUP
Panel Checks (Power On - Both Unit Switch Off)
1. Apply three-phase power and verify its value. Volt-
age imbalance should be no more than 2% of the
average voltage ......................................................
2. Apply 120 VAC (110 VAC for 50 Hz units) and
verify its value on the terminal block in the Power
Panel. Make the measurement between Termi-
nals 5 and 2 of XTBC2. The voltage should be
120 VAC plus or minus 10% .....................................
3. Program or verify the Cooling Setpoints, Program
Setpoints, and Unit Options. Record the values
in the Setpoints Entry List table ................................
4. Place the unit into Service Mode and cycle each
condenser fan to ensure correct rotation .................
If the chiller is equipped with VSD fans, the
cycling condenser fan cannot be used to con-
firm phase sequence. Use a phase checker or
temporarily bypass the VSD before starting a
compressor.
5. Turn System 2 off and leave System 1 running.
Refer to
Section 8 – Unit Operations
(Form
QTC3-NM1)
,
Unit Keys, Option 2
for more infor-
mation on System Switches ......................................
6. Connect a manifold gauge to system 1 suction
and discharge service valves. ...................................
7. Place the Unit Switch in the control panel to the
ON position. ...............................................................
NOTE:
The chilled liquid setpoint may need to
be temporarily lowered to ensure all compres-
sors cycle ON.
As each compressor cycles ON, ensure that the
discharge pressure rises and the suction pressure
decreases. If this does not occur, the compressor
being tested is operating in the reverse direction and
must be corrected.
8. Verify proper compressor rotation and then turn
the Unit Switch to OFF ..............................................
NOTE:
This unit uses scroll compressors, which
can only operate in one direction. Failure to ob-
serve this will lead to compressor failure.
9. Turn System 1 OFF and System 2 ON (two system
units only). Refer to
Section 8 – Unit Operations
(Form QTC3-NM1), Unit Keys
for more information ...
10. Place the Unit Switch in the control panel to the
ON position. ...............................................................
NOTE:
The chilled liquid setpoint may need to
be temporarily lowered to ensure all compres-
sors cycle ON.
As each compressor cycles ON, ensure that the dis-
charge pressure rises and the suction pressure
decreases. If this does not occur, the compressor
being tested is operating in the reverse direction and
must be corrected.
11. Ensure that the Data Logging feature has been
enabled ......................................................................
12. Verify correct compressor rotation and then turn
the Unit Switch to OFF...............................................
Summary of Contents for QTC3040T
Page 10: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 34: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 73: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 110: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 168: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...