139
QUANTECH
FORM QTC3-NM1
ISSUE DATE 08/03/2022
SECTION 7 – UNIT CONTROLS
7
Option 13 – Soft Start Enable/Disable
S O F T S T A R T
D I S A B L E D
SOFT START “DISABLED” MUST be selected on all
chillers.
This message may not be viewable on non-European
chillers.
Option 14 – Unit Type
U N I T T Y P E
L I Q U I D C H I L L E R
The UNIT TYPE message cannot be modified under
the unit keys.
“Liquid CHILLER” must be displayed, or
damage to compressors or other compo-
nents will occur if operated in the HEAT
PUMP or CONDENSING UNIT modes.
If unit type needs to be changed to make the unit a
liquid chiller, remove power and then remove the
jumper between J11-7 and J11-12 on the I/O Board.
Reapply power to the
micro panel
and the
micropro-
cessor
will store the change.
Option 15 – Refrigerant Type
R E F R I G E R A N T T Y P E
R – 4 1 0 A
Refrigerant type R-410A must be selected under Ser-
vice Mode. Refrigerant type is displayed under the
OPTIONS key, but is only programmable in Service
Mode.
Incorrect programming may cause dam-
age to compressors.
Option 9 – Condenser Fan Control Mode
F A N C O N T R O L
D I S C H A R G E P R E S S U R E
Condenser fans are controlled by discharge pressure
only. This mode must be chosen.
or
F A N C O N T R O L
A M B I E N T & D S C H P R E S S
Do not select this option on R-410A chillers.
Option 10 – Manual Override Mode
M A N U A L O V E R R I D E M O D E
D I S A B L E D
This option allows overriding of the daily schedule
that is programmed. MANUAL OVERRIDE MODE –
DISABLED indicates that override mode has no effect.
or
M A N U A L O V E R R I D E M O D E
E N A B L E D
Manual Override Mode is enabled. This is a service
function and when enabled, will allow the unit to start
when shut down on the daily schedule. It will auto-
matically be disabled after 30 min.
Option 12 – Power Fail Restart
P O W E R F A I L R E S T A R T
A U T O
M
A T I C
Chiller auto restarts after a power failure.
P O W E R F A I L R E S T A R T
M
A N
U A L
After a power failure, the UNIT switch must be tog-
gled before restart at the unit is allowed. NORMALLY
MANUAL RESTART should NOT BE SELECTED.
Summary of Contents for QTC3040T
Page 10: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 34: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 73: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 110: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 168: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...