SECTION 7 – UNIT CONTROLS
7
Unit Warning
The following messages are not unit safeties and will
not be logged to the history buffer. They are unit warn-
ings and will not auto-restart. Operator intervention is
required to allow a restart of the chiller.
! ! L O W B A T T E R Y ! !
C H E C K P R O G / S E T P / O P T N
The Low Battery Warning can only occur at unit pow-
er-up. On micro panel power-up, the RTC battery is
checked. If a low battery is found, all programmed
setpoints, program values, options, time, schedule, and
history buffers will be lost. These values will all be re-
set to their default values which may not be the desired
operating values. Once a faulty battery is detected, the
unit will be prevented from running until the PRO-
GRAM key is pressed. Once PROGRAM is pressed
the anti-recycle timers will be set to the programmed
anti-recycle time to allow the operator time to check
setpoints, and if necessary, reprogram programmable
values and options.
If a low battery is detected, it should be replaced as
soon as possible. The programmed values will all be
lost and the unit will be prevented from running on the
next power interruption. The RTC/battery (031-02565-
000) is located at U5 on the microboard.
I N C O R R E C T
U N I T T Y P E
This indicates the condensing unit jumper is installed
between J11-12 and J11-7. This jumper must be re-
moved to operate the chiller.
Summary of Contents for QTC3040T
Page 10: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 34: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 73: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 102: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 110: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 168: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...