4100-I ACT Wood Insert
Page 22
April 19, 2010
R
250-7201F
Odors and vapors released during initial
operation.
• Curing of high temperature paint.
• Open windows for air circulation.
Odors may be irritating to sensitive individuals.
CAUTION
1.
Initial (cold) startup:
Leave fan off until your insert is hot
and a good coal bed is established, approximately 0 min-
utes after fuel is lit.
2.
High Burn Setting:
The fan may be left on throughout the
burn.
.
Medium or Medium High Burn Setting:
The fan should
be left off until a good burn is established, then turned on a
medium or high rate.
4.
Low Burn Setting:
The fan tends to cool the insert. Leave
fan off until the burn is well established; then, if you wish, turn
the fan on at a low rate.
5. The fan is equipped with a rheostat (speed control). The
highest fan speed is obtained by turning the rheostat on, then
adjusting back towards “OFF” as far as possible without turn-
ing the fan off. For a low fan speed, turn the control knob
clockwise as far as possible.
Blower Operating Instructions
For maximum operating efficiency with the lowest emissions,
follow these operating procedures:
1. Regardless of desired heat output, when loading insert,
burn your Quadra-Fire with both air controls wide open for
a minimum of 5 to 15 minutes.
2. Regulate burn rate (heat output) by using the Primary Con-
trol (center control under ashlip). The Start-Up Air Control
(right control) is mainly for initial start-up and reloading.
. Heat output settings: Follow burn rate instructions listed
below.
4.
Burn only dry, well-seasoned wood.
These are approximate settings, and will vary with type of
wood or chimney draft.
Burn Rates & Operating Efficiency
STARTING FIRE
: Open both controls (push in) completely.
After a wood load has been burning on high for 5 to 15 minutes
or longer for very large pieces, close the Start-Up Air Control
(bottom rod) by pulling it out.
HIGH:
Leave the Primary
Air Control fully open (immediately
under the ashcatcher). It is especially important to fully open
both controls when reloading the insert as failure to do so could
result in excessive emissions, also referred to as ‘opacity’.
After a wood load has been burning on high for 5 to 15
minutes on High to achieve the following burn rates set
the controls as listed below:
MEDIUM HIGH:
Close the Primary Air Control to 1-1/4 inch to
2-1/2 inch (1mm to 6mm) open. Start-Up Air is closed.
MEDIUM LOW
: Close the Primary Air Control to 1.0 inch to
1-1/4
inch (25mm to 1mm) open. Start-Up Air is closed.
LOW:
Gradually close down the Primary Air Control by
pulli
ng out making sure to maintain flames in the insert. Start-
Up Air is closed. It is very important to maintain flames in your
insert during the first few hours of a low burn to avoid exces-
sive air pollution.
Opacity
Opacity is the measure of how clean your insert is burning and
is measured in percentages. An opacity of 100% in the smoke
column from a chimney will totally obscure an object. Whereas
0% opacity means that no smoke column can be seen. A peri-
odic check of the opacity emitted from your chimney will enable
you to burn your insert as smoke free as possible.
BTU / Hr
Close Start-Up Air
Primary Control
Below 10,000
After 5-15 min
Pull to Stop
10,000 - 15,000
After 5-15 min
1.0 in to 1-1/4 in open
15,000 - 0,000
After 5-15 min
1-1/4 in to 2.5 in open
Maximum Heat
After 5-15 min
Fully Open
NOTE:
• Build fire on brick firebox floor.
•
Do NOT use grates, andirons or other methods to support fuel.
It will adversely affect emissions.
Fire Risk
• Do NOT operate with Start-Up Air Control in
open position in excess of 15 minutes.
• Risk of extreme temperatures!
WARNING
Prolonged operation with Start-Up Air Control in open
position may cause combustible materials around
appliance to exceed safe temperature limits.