No.
Output
Type
Active
Restore
0035
Follow Input
Active when a specific input number has been activated. It allows the following options to be
programmed:
-
Follow Type (Follow, Timed, Latched, Code Reset);
-
Follow What (Input, Sub-Area, Area);
-
Follow When (Always, When Armed, When Disarmed);
-
Input to Follow (between 1 to 64)
0037
Restore 1
At code entry to arm. The normal state of this
input is 0v and it changes to 12v when activated.
After 3 seconds
0038
Restore 2
Activates whenever an additional area is armed.
The normal state of this input is 0v and it
changes to 12v when activated.
When disarmed
0039
PIR Latch 1
When armed (and in Walk Test)
At alarm, or when disarmed
0040
PIR Latch 2
This is the inverse polarity to PIR Latch 1
At alarm, or when disarmed
0041
AC Mains
Good
Output showing the 230v mains supply is present
0042
PIR LED
Enable
This output activates during walk test
0043
Follow Test
Output will activate only when tested from the Engineer Menu ‘Test Outputs’ in the ‘Engineer Tests’.
This output can be used as additional facility for testing the operation of a Bell. An output
programmed to one of these configurations (43 and 44) may be used to trigger a relay to break the
hold-off connection to the Bell – or even to provide the hold-off directly.
0044
Off During
Test
Output is normally active and will deactivate only when tested from the Engineer Menu ‘Test Outputs’
in the ‘Engineer Tests’.
Same as 43 but opposite activation.
0048
Walk Test
This output is active during walk test, and will only deactivate when all detectors have been tested
0049
Detector
Masked
If any detector goes into ‘mask’ condition the
output will activate
When masking fault clears
0050
Follow 24
Hour
If any input programmed as ’24 Hour’ activates
When input is restored
0051
Line/GPRS
Fault
When Telephone or GPRS Line Fault is present
When fault clears
0052
AC Mains Fail
After pre-set time without mains power
On restoration of mains
0053
Battery Fault
When battery disconnected or load fail detected
At next valid code entry
0054
Low Volts
When less than 11.2v are present
When fault clears
0055
Global Fault 1
(Grade 2)
Activates if any fault occurs only when system is
armed
When all faults cleared
0056
Global Fault 2
(Grade 3)
Activates if any fault occurs at any time
When all faults cleared
0057
German Relay
For future development. Do Not Use.
0058
Guard Code
Used
When ‘guard’ code used on the system
After 60 seconds
0059
Engineer
Access
When entering Engineer Mode
When leaving Engineer Mode
0060
Follow Power
Up
At power up
Live for 45 seconds
0063
Test UK STU
Activates when a test call is sent
When test completed
72
Enforcer Installation Guide
102017854 - V01