SS-BEAM1224

Conventional Beam Detector

Installation Guide

 

3

Transmitter/receiver built into same unit

 

3

Six user-selectable sensitivity levels

 

3

5m to 70m (use BEAMLRK beyond 70m) protection range

 

3

Removable plug-in terminal blocks

 

3

Digital display – no special tools required

 

3

Built-in automatic gain control compensates for signal   

 

deterioration from dust buildup

 

3

Optional remote test station

 

3

Optional long-range kit (BEAMLRK) for applications in   

 

excess of 70m

 

3

Optional multi-mount (BEAMMMK) providing ceiling or wall  

 

mount capability with increased angular adjustment

FEATURES

PRODUCT DESCRIPTION

The FireSense SS-BEAM1224 is a conventional projected beam smoke sensor. It is uniquely suited for 

protecting open areas with high ceilings where other methods of smoke detection are difficult to install and 

maintain. Alignment is quickly accomplished via an optical sight and a 2-digit signal strength meter incorporated 

into the product.

Listed for operation from -30ºC to 55ºC, the SS-BEAM1224 can be used in open area applications to provide early 

warning in environments where temperature extremes exceed the capability of other types of smoke detection.

The SS-BEAM1224 consists of a transmitter/receiver unit at the head end and a reflector. When smoke enters the 

area between the unit and the reflector, it causes a reduction in the signal and when the smoke level reaches the 

predetermined threshold, an alarm is activated.

The SS-BEAM1224 has four standard sensitivity selections along with two Acclimate settings. When either of the 

two Acclimate settings are selected the detector will automatically adjust its sensitivity using advanced software 

algorithms to select the optimum sensitivity for the specific environment.

CABLING REQUIREMENTS

SS-BEAM1244

 

3

Requires 2 core for 24Vdc

 

3

Requires 2 core for initiating alarm contact

Summary of Contents for SS-BEAM1224

Page 1: ...e sensor It is uniquely suited for protecting open areas with high ceilings where other methods of smoke detection are difficult to install and maintain Alignment is quickly accomplished via an optical sight and a 2 digit signal strength meter incorporated into the product Listed for operation from 30ºC to 55ºC the SS BEAM1224 can be used in open area applications to provide early warning in envir...

Page 2: ...ce the alignment procedure is completed 3 3 Ensure that the appropriate number of reflectors are used for the installed distance Distances between 70 100m require additional reflectors 4 total The BEAMLRK accessory should be used in these cases 3 3 Ensure that the line of sight between the detector and reflector is clear and that reflective objects are not too near TECHNICAL SPECIFICATIONS Protect...

Page 3: ...the mirror in order to locate the reflector If the distance between the reflector and the detector is large it is helpful to place a brightly coloured object on the wall near the reflector to aid in seeing the reflector in the alignment mirror 3 Once the reflector has been located begin to adjust both the horizontal and vertical alignment knobs so that the reflector becomes centred in the alignmen...

Page 4: ...e Note The display will continue to read Lo until the detector receives enough light from the reflector to continue with the fine adjustment step Note In alignment mode indicated by the yellow LED and the numeric display the sensitivity select and test switches are disabled 3 With the display reading a numeric value begin adjusting the horizontal and vertical alignment knobs one at a time in the d...

Page 5: ...e electronic gain setting Once complete the yellow LED will stop blinking and the green LED will begin blinking This indicates that the gain adjustment was successful Note Use caution not to block the line of sight between the detector and reflector in this step 5 Install the outer aesthetic ring by snapping it onto the outer housing Note If the outer aesthetic ring has been painted ensure that th...

Page 6: ...tomatically adjust its sensitivity using advanced software algorithms to select the optimum sensitivity for the environment The sensitivity will be continuously adjusted within the ranges specified in the chart below Sensitivity Setting Percent Obscuration Display Reading Acceptable Distance Between Detector Reflector Feet Acceptable Distance Between Detector Reflector Meters Level 1 25 25 16 4 12...

Page 7: ...l Over Range Off 2 Quick Blinks Blink Off Increase of reflected signal Open Off Open Inspect line of sight between de tector and reflector for reflective objects in the pathway Trouble Beam Blockage Response Off 4 Quick Blinks Off Off Beam blockage Open Off Open Remove blockage Faulty unit Initialisation Power On Off Blink Until Complete Blink Off Apply power from discharged state Open Off Close I...

Reviews: