Input Types
Number
Input
types
Operation
0
Unused
Factory
default.
Input is disabled.
1
Fire
Active at all times. Audible Response: Differentiated Internal sound. Pulsed external sound.
Communicator: ‘Fire’ signal
2
Gas
Active at all times. Audible Response: Full ex Internal sound. Communicator: ‘Gas’ signal
3
PA#
Active at all times. Audible Response: Differentiated Internal sound. Full external sound.
Communicator: ‘Personal Attack’ and ‘Input PA’ signals
4
Silent PA#
Active at all times. Audible Response: None
Communicator: ‘Personal Attack’ and ‘Input PA’ signals
5
Tamper
When disarmed: Audible Response: Internal only. Communicator: ‘Tamper’ signal.
When armed: Audible Response: Full ex Internal sound. Communicator: ‘Tamper’ signal.
6
Instant
Active when armed: Audible Response: Full ex Internal sound.
Communicator: ‘Burglary’ signal
7
Entry
Delay1#$
Active when armed: Initiates 'Entry Timer 1' when door open. If system not disarmed before entry
time expires then: Audible Response: Full Ex Internal sound.
Communicator: ‘Burglary’ signal. NOTE: See type 43 for Entry Delay2
8
Follow$
Active when armed, except during entry time. (Acts as an instant input if an Entry Delay input hasn’t
been activated beforehand).
Audible Response: Full ex Internal sound.
Communicator: ‘Burglary’ signal.
12
Switcher
Active at all times in armed and disarmed modes. No audible or communication alarms will be
created. When activated it can trigger the associated output for switching external equipment. If the
“Special Log” attribute is enabled for this input an SMS message will be sent each time the input is
activated.
Example: This kind of input type can be used to control CCTV. The concept is that when a switcher
input type is activated, there is an output associated with it following that input (the most used
solution is the use of output type – 0035). The switcher input is connected to a detector located next
to a CCTV camera and the output is connected to video recording / transmitting equipment. If the
detector is activated in armed or disarmed mode then the recording or transmission will start.
13
24 Hour
When armed: Audible Response: Full Ex Internal sound; Communicator: ‘24hr Alarm’ signal.
When disarmed: Audible Response: Full Ex Internal sound; Communicator: ‘24hr Alarm’ signal
if enabled in “Alarm Responses” menu.
16
Fault
Active when armed or disarmed: Audible Response: internal sounder.
Communicator: Fault event.
If armed only: Activates ‘Global Fault 1’ output type.
If disarmed or armed: Activates ‘Global Fault 2’ output type.
Note that the ‘Technical Fault’ output type is triggered every time a fault is active including when the
fault input type is active.
17
Arming
Control
Active during arming procedure: No audible or communicator response. Prevents system being
armed whilst the input is in an active state.
19
Disarm
Only*
Active when armed: Accepts input from keyswitch (or equivalent) to disarm the area(s) assigned to it.
20
Keyswitch
Latched*
Accepts input from keyswitch (or equivalent) to arm/disarm the area assigned to it.
Arming includes normal exit time, etc. Requires latching switch action. Normal operation is open
circuit to arm the system, and close circuit to disarm the system.
Enforcer Installation Guide
102017854 - V01
69
Summary of Contents for Enforcer 64
Page 1: ...102017854 V01 Software V12 0 Enforcer 64 Installation Guide...
Page 85: ...Notes Enforcer Installation Guide 102017854 V01 85...
Page 86: ......
Page 87: ......
Page 88: ......