P r o g r a m m a E l e c t r i c A B
Z P - B M 0 1 E R 0 7 A
7 2
E G I L
13 Specifications
13.1 EGIL
General
Specifications are subject to change without notice.
Application field:
The instrument is intended
for use in medium voltage
substations and industrial
environments up to 130 kV
Mains voltage:
115/230 V AC
(switchable), 50-60 Hz
Languages:
English, German, French,
Spanish or Swedish
Operating temperature:
0 to +50°C (+32 to +122°F)
Storage temperature:
-40 to +70°C (-40 to +158°F)
Humidity:
5% to 95% RH, Non-
condensing
Dimensions:
360 x 210 x 190 mm (14.2"
x 8.3" x 7.5")
Dimensions transpor t case:
420 x 300 x 230 mm
(16.5" x 11.8" x 9.0")
Weight:
6.3 kg (14 lbs). 10 kg
(22 lbs) with accessories
and carr ying case
CE-marking
EMC:
EMC Directive 89/336/EEC
am. by 91/263/EEC,
92/31/EEC and 93/68/
EEC
LVD:
Low Voltage Directive 73/
23/ EEC am. by 93/68/
EEC
Measurement time:
1 to 100 s
Resolution:
0.1 to 10 ms
Time base accuracy:
0.05% of the reading
± resolution
Current measurement
Range:
±25 A per channel, sum of
currents is measured
Resolution:
25 mA
Accuracy:
1% of the reading ±100 mA
Working voltage:
250 V AC/DC
Breaker operation
Sequences:
C, O, C-O, O-C, O-C-O.
Continuous current:
5 A
Max current:
25 A during 300 ms, rest
time 1 min
Contact function:
Two independent control
functions.
Contact characteristics:
Non bouncing, Closing time
maximum 0.1 ms.
Make/Break capacity:
25 A, 250 V (AC or DC) per
contact function.
Star t breaker operation: By rotar y switch.
Pulse length:
Adjustable in steps of
10 ms
Pulse delay:
Adjustable in steps of
10 ms
Working voltage:
250 V AC/DC
TIMING
Number of channels:
3 with common ground
Status thresholds
Closed:
< 10
Ω
±20%
Resistor:
10
Ω
±20% to 3 k
Ω
±20%.
Open:
> 3 k
Ω
±20%
Open Circuit voltage:
24 V ±20%
Shor t circuit current:
100 mA ±20%
AUX 1&2
Number of channels:
2, galvanically isolated
Contact-sensing (Dry)
Status Threshold:
Closed:
< 600
Ω
±30%
Open:
> 600
Ω
±30%
Open Circuit voltage:
20 V ±20% DC
Shor t circuit current:
25 mA ±20%
Voltage sensing (Wet)
Status Threshold:
8 – 13 V
< 8 V – Open Indication
> 13 V – Close Indication
Polarity insensitive
Working voltage:
250 V AC/DC
MOTION (Optional)
Number of channels:
1 independent
Max Cable length:
10 m
Input
Range:
-4 to +4 V
Resolution:
2 mV
Accuracy:
1% of the measurement
range
Transducer resistance:
1 k
Ω
to 5 k
Ω
Input impedance:
150 k
Ω
Output
Open circuit voltage:
4,092 V ±4 mV
Shor t circuit current:
115 mA
Summary of Contents for EGIL BM-19070
Page 1: ...EGIL Breaker Analyzer User s Manual...
Page 2: ......
Page 7: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 7 E G I L...
Page 9: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 9 E G I L...
Page 15: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 1 5 E G I L...
Page 19: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 1 9 E G I L...
Page 20: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 E R 0 7 A 2 0 E G I L 5 Control panel...
Page 47: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 4 7 E G I L...
Page 49: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 4 9 E G I L...
Page 61: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 6 1 E G I L...
Page 65: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 6 5 E G I L...
Page 75: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 7 5 E G I L...
Page 78: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 E R 0 7 A 7 8 E G I L...
Page 79: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 7 9 E G I L...
Page 80: ...Subject to change without notice Printed matter No ZP BM01E R07A Doc BM0087JE...