P r o g r a m m a E l e c t r i c A B
Z P - B M 0 1 E R 0 7 A
3 8
E G I L
You can also choose the option:
Cls:Upper Point
<At Cls of Main>
Now you define whether the lower point will be related to
the upper point by distance or by time.
Define the distance from the upper point:
Cls:Lower Point
<Distance> Time
Dist. Below Upp.
0010.0 mm
or define time before the upper point:
Cls:Lower Upp.
010 ms
Time Before Upp.
010 ms
Option - End
Display
In this menu, you can view data and calculated parameters
from the latest measurement on the display. This can be
useful if, for example, you do not want to print a report or
you want to perform a thorough analysis of the breaker’s
state in relation to time. If you access this menu without
having performed a measurement, you will get the error
message:
Memory empty
There are four different values on the display:
• moment in time
• coil current
• measured value on the analog channel
• contact status on the time channel
The time relates to the beginning of the measurement. For
each selected time, the corresponding value measured in
that instant is shown. By changing the time, you can see
the measured values for any time within the used measur-
ing time.
If you press ENTER, the calculated parameters are shown.
These are the same parameters that are shown in the
printout.
Example:
The measured value below is displayed in the display
window:
0041.7 ms 1.566 A
60.3 mm
CCC CO
At the selected time displayed in the upper left corner, the
following value has been measured for coil current:
0041.7 ms 1.566 A
60.3
CCC CO
In the lower left corner, you can see the size value that you
defined to measure with the analog channel. In this case, it
is motion. During measurement of motion, the value
represents the moving contact’s distance from the break-
er’s stable open position.
Note!
If the analog channel is not activated
(position Off), this field is empty.
0041.7 ms 1.566 A
60.3 mm
ORC CO
Time channel’s status:
0041.7 ms 1.566 A
60.3 mm
ORC CO
Status:
O = open
R = resistor
C = close
Note!
If you enter a time that exceeds the
measure time used, the display window
shows dashes instead of measured
values.
1000.1 ms
——
——
——
Calculated parameters
Press ENTER to see the calculated parameters. By
continuing to press ENTER, you can step through all the
calculated parameters. To view a previously shown
parameter, press the ESC key.
Note!
You must choose MOTION from the
ANALOG CHANNEL to display the param-
eters related to motion measurement.
The calculated parameters are distinguishable between the
different types of operations. The following curve diagram
refers to the description of the calculated parameters.
Summary of Contents for EGIL BM-19070
Page 1: ...EGIL Breaker Analyzer User s Manual...
Page 2: ......
Page 7: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 7 E G I L...
Page 9: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 9 E G I L...
Page 15: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 1 5 E G I L...
Page 19: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 1 9 E G I L...
Page 20: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 E R 0 7 A 2 0 E G I L 5 Control panel...
Page 47: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 4 7 E G I L...
Page 49: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 4 9 E G I L...
Page 61: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 6 1 E G I L...
Page 65: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 6 5 E G I L...
Page 75: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 7 5 E G I L...
Page 78: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 E R 0 7 A 7 8 E G I L...
Page 79: ...P r o g r a m m a E l e c t r i c A B Z P B M 0 1 D R 0 7 A 7 9 E G I L...
Page 80: ...Subject to change without notice Printed matter No ZP BM01E R07A Doc BM0087JE...