Serial Interface

RS-232C and RS-422 serial interface. Used to connect with a host (PLC).

Pin Arrangement

Pin No.

Signal

Condition

1

FG

Frame  Ground

2

SD

Send Data (RS-232C)

3

RD

Receive Data (RS-232C)

4

RS

Request Send (RS-232C)

5

CS

Clear Send (RS-232C)

6

NC

No Connection

7

SG

Signal Ground

8

CD

Carrier Detect (RS-232C)

9

TRMX

Termination (RS-422)

10

RDA

Receive Data A (RS-422)

11

SDA

Send Data B (RS-422)

12

*1

RESERVE RESERVE

13

*1

RESERVE RESERVE

14

VCC

5V±5% Output 0.25A

15

SDB

Send Data B (RS-422)

16

RDB

Receive Data B (RS-422)

17

NC

No Connection

18

CSB

Clear Send B (RS-422)

19

ERB

Enable Receive B (RS-422)

20

ERB

Enable Receive B (RS-232C)

21

CSA

Clear Send A (RS-422)

22

ERA

Enable Receive A (RS-422)

23

NC

No Connection

24

NC

No Connection

25

NC

No Connection

Recommended Connector : Dsub 25 pin plug XM2A-2501 <made by OMRON Corp.>
Recommended Cover

: Dsub 25 pin Cover XM2S-2511 <made by OMRON Corp.>

Use Jack Screw XM2Z-0071 <made by OMRON Corp.>
when needed.

Recommended Cable

: CO-MA-VV-SB5P x 28AWG <made by HITACHI Cable Ltd.>

*1    As pin no.12 and 13 are reserved, do not connect anything with them.

Use M2.6 x 0.45 pitch set screws to attach the cabler to the LogiTouch unit.

When connecting to external controllers, refer to the “LogiTouch

External Communication Unit Connection Manual”(included in
the “Logic Program Developer Software LogiTouch Editor”)

4

 Interfaces

Summary of Contents for LogiTouch GLC150-BG41-RSFL-24V

Page 1: ...s load control power turning ON an incorrect output signal or malfunction could cause an accident to occur Be sure to design a program that will ensure the safety of your system in in the event of a...

Page 2: ...power cord is unplugged from the power supply Be sure to reattach the LogiTouch terminal block s plastic cover after completing any terminal wiring If this cover is not reattached an electric shock c...

Page 3: ...cident Be sure to secure all wiring terminal screws in place with the designated torque Screws and terminals that become loose can cause a short circuit fire or accident Be sure that metal filings or...

Page 4: ...st all be in accordance with Class I Division 2 wiring methods Article 501 4 b of the National Electrical Code NFPA 70 or as speci fied in Section 18 152 of the Canadian Electrical Code for units inst...

Page 5: ...This Guide Option Items sold separately LogiTouch Series User Manual GLC150 MM01 Flex Network Cables Logic Program Developer Software LogiTouch Editor Data Transfer Cable GPW CB02 50m FN CABLE2050 31...

Page 6: ...cuit I Flex Network Connector J Flex Network LED Operation Mode 1 Controller Operation Mode 2 LED Color OFFLINE STOP Green Constant In Operation RUN Green Constant In Operation STOP Green Flashing In...

Page 7: ...will monitor the LT unit s circuits Contact Rating 0 15A AC125V Resistance Load 0 6A DC24V Resistance Load Operating Time Set Time at 20 o C 4ms or less Recover Time Reset Time at 20 o C 4ms or less...

Page 8: ...S 422 19 ERB Enable Receive B RS 422 20 ERB Enable Receive B RS 232C 21 CSA Clear Send A RS 422 22 ERA Enable Receive A RS 422 23 NC No Connection 24 NC No Connection 25 NC No Connection Recommended C...

Page 9: ...nformation about Flex Network or connectable Flex Network I O units see the Flex Network User Manual 5 Installation Before installing the LogiTouch into a cabinet or panel check that the installation...

Page 10: ...s show the four 4 fastener insertion slot locations Insert each fastener s hook into the slot and pull it back until the hook catches Insertion Slots Panel Hook Tightening the screws with too much for...

Page 11: ...unit will result in excess noise and vibration Wherever possible use thick wires max 2 mm2 for power terminals and twist the wire ends before attaching the ring terminals Be sure to use the following...

Page 12: ...ttaching a wire to the LogiTouch s rear face FG terminal on the Power Input Terminal Block be sure to create an exclusive ground 1 Inside the LogiTouch unit the SG Signal Ground and FG Frame Ground te...

Reviews: