11
6
Wiring
• To prevent an electric shock, prior to connecting the LogiTouch’s power
cord terminals to the power terminal block, be sure that the LogiTouch’s
power supply is turned OFF, via a breaker, or similar unit.
• The GLC150-BG41-RSFL-24V unit is designed to use only DC24V
input. Any other power level can damage both the LogiTouch and
the power supply.
• To prevent an electric shock or equipment damage, be sure to reattach
the plastic cover to the terminal block after completing any wiring.
WARNINGS
• To avoid a short caused by loose ring terminals, be sure to use
ring terminals with an insulating sleeve.
*1
• When the FG terminal is connected, be sure the wire is grounded. Not
grounding the LogiTouch unit will result in excess noise and vibration.
• Wherever possible, use thick wires (max. 2 mm
2
) for power terminals, and
twist the wire ends before attaching the ring terminals.
• Be sure to use the following size ring terminals.
Connecting the LogiTouch Power Cord
When connecting the power cord, be sure to follow the procedures given below.
1. Confirm that the LogiTouch’s Power Cord is unplugged from the power supply.
2. Use a screwdriver to remove the Power Input Terminal Block’s clear plastic cover.
3. Unscrew the screws from the middle three (3) terminals, align the Ring
Terminals and reattach the screws.
4. Confirm that the wires are connected correctly.
5. Replace the Power Input Terminal Block’s clear plastic cover.
Rear View
FG
–
+
Power Input
Terminal Block
under 6.0mm [0.24in]
over
φφφφφ
3.2mm [0.13in]
The torque required to tighten these screws is 0.5 to 0.6Nm.
*1
Suggested Ring Terminal : V2-MS3 (made by JST)
FG
–
+