CAUTIONS

Wiring Layout:

- Be sure that all LogiTouch input/output signal lines are isolated from all power

wiring or power cables, via a separate wiring duct. This is to prevent excessive

noise, which can cause a unit malfunction.

Installation:

- Be sure all data cables attached to the LogiTouch are securely connected. If all

connector pins do not make complete contact, incorrect input or output signals

can result.

General Wiring:

- To prevent shocks or malfunctions, LogiTouch’s FG (earth) wire should be

grounded according to the following:

1) Be sure to use a maximum grounding resistance of 100

 or less.

2) A grounding wire of 2mm

2

 or larger should be used.

- Be sure to confirm that the LogiTouch's operating voltage and wiring terminal

locations are correct. If either are incorrect, it can cause a fire or accident.

- Be sure to secure all wiring terminal screws in place with the designated torque.

Screws and terminals that become loose can cause a short circuit, fire or accident.

- Be sure that metal filings or wiring remnants do not fall inside the LogiTouch,

since they can cause a fire, accident, or malfunction.

LogiTouch Operation and Maintenance:

- Be sure to read the LogiTouch’s manual and on-line help information carefully

before performing program changes, forced output, or utilizing the RUN, STOP

or PAUSE commands while the LogiTouch is in operation. Mistakes concerning

the use of these items can cause an accident or equipment or damage.

- The LogiTouch's liquid crystal display contains a powerful irritant and if for any

reason the panel is damaged and this liquid enters your eye, flush your eye for 15

minutes with running water and contact a physcian.

LogiTouch Unit Disposal:

- Be sure to dispose of the LogiTouch unit in a manner appropriate to your country’s

industrial machinery disposal standards.

Summary of Contents for LogiTouch GLC150-BG41-RSFL-24V

Page 1: ...s load control power turning ON an incorrect output signal or malfunction could cause an accident to occur Be sure to design a program that will ensure the safety of your system in in the event of a...

Page 2: ...power cord is unplugged from the power supply Be sure to reattach the LogiTouch terminal block s plastic cover after completing any terminal wiring If this cover is not reattached an electric shock c...

Page 3: ...cident Be sure to secure all wiring terminal screws in place with the designated torque Screws and terminals that become loose can cause a short circuit fire or accident Be sure that metal filings or...

Page 4: ...st all be in accordance with Class I Division 2 wiring methods Article 501 4 b of the National Electrical Code NFPA 70 or as speci fied in Section 18 152 of the Canadian Electrical Code for units inst...

Page 5: ...This Guide Option Items sold separately LogiTouch Series User Manual GLC150 MM01 Flex Network Cables Logic Program Developer Software LogiTouch Editor Data Transfer Cable GPW CB02 50m FN CABLE2050 31...

Page 6: ...cuit I Flex Network Connector J Flex Network LED Operation Mode 1 Controller Operation Mode 2 LED Color OFFLINE STOP Green Constant In Operation RUN Green Constant In Operation STOP Green Flashing In...

Page 7: ...will monitor the LT unit s circuits Contact Rating 0 15A AC125V Resistance Load 0 6A DC24V Resistance Load Operating Time Set Time at 20 o C 4ms or less Recover Time Reset Time at 20 o C 4ms or less...

Page 8: ...S 422 19 ERB Enable Receive B RS 422 20 ERB Enable Receive B RS 232C 21 CSA Clear Send A RS 422 22 ERA Enable Receive A RS 422 23 NC No Connection 24 NC No Connection 25 NC No Connection Recommended C...

Page 9: ...nformation about Flex Network or connectable Flex Network I O units see the Flex Network User Manual 5 Installation Before installing the LogiTouch into a cabinet or panel check that the installation...

Page 10: ...s show the four 4 fastener insertion slot locations Insert each fastener s hook into the slot and pull it back until the hook catches Insertion Slots Panel Hook Tightening the screws with too much for...

Page 11: ...unit will result in excess noise and vibration Wherever possible use thick wires max 2 mm2 for power terminals and twist the wire ends before attaching the ring terminals Be sure to use the following...

Page 12: ...ttaching a wire to the LogiTouch s rear face FG terminal on the Power Input Terminal Block be sure to create an exclusive ground 1 Inside the LogiTouch unit the SG Signal Ground and FG Frame Ground te...

Reviews: