Figure 2: Output blocks mounting.
3.3 Cooling water
The cooling water can be connected to the left or right side of the power supply. The
unit is shipped with the water inputs on the left hand side. Two female ¼” NPT
connections are provided. If required, move the water fittings to the right hand side.
Keep the input towards the back of the unit and output towards the front of the unit
location. The unit will not operate if the water flow is reversed.
Turn on the cooling water flow and verify that it meets the minimum requirements as
given in section
1.8. on page 5. Check for any water leaks on the inlet, outlet and
heating coil. Tighten connections if necessary. Also check for any water leaks inside the
unit that could have been caused by shipping, and tighten any hose clamps if
necessary.