28
OUTPUT- 2
(Terminals 23 & 24)
OUTPUT- 3
(Terminals 25 & 26)
OUTPUT- 4
(Terminals 27 & 28)
The Output-2, Output-3 and Output-4 are available through plug-in modules. The modules are factory configured for either
Relay or SSR. The connection descriptions are the same as those described for Output-1.
OUTPUT- 5
(Terminals 38 & 39)
The Output-5
is a DC Linear (0/4-20 mA) Current or (0-5/10V) Voltage output for
plug-in module
retransmission, as shown in Figure 11.3 ( c ).
Figure 11.3 (c)
38
39
POWER SUPPLY
(Terminals 1 & 2)
Figure 11.4
Caution
The indicator is designed for installation in an enclosure which provides adequate protection against electric
shock. Local regulations regarding electrical installation should be rigidly observed. Consideration should be
given to prevention of access to the Power Supply terminals by unauthorized personnel.
As standard, the indicator is supplied with power connections suited for 85 to 264 VAC line supply. Use well-insulated copper
2
conductor wire of the size not smaller than 0.5mm for power supply connections. Connect Line (Phase) supply line to terminal
1 and the Neutral (Return) supply line to terminal 2 as shown in Figure 11.4. The indicator is not provided with fuse and power
switch. If necessary, mount them separately. Use a time lag fuse rated 1A @ 240 VAC.
User Manual
neuro 100EX
SERIAL COMMUNICATION PORT
(Terminals 7 & 8)
Figure 11.5
Line
Neutral
1 (L)
2 (N)
2 Pole
Isolating Switch
Fuse
Power Supply
Terminal
Terminating Resistor
Screened Cable
Twisted
Wire Pair
(100 to 150 Ohms)
8 (B-)
7 (B+)
HOST
B-
B+
Master Device
Serial Comm.
Terminals