45
Models
6K
6KS
10K
10KS
10K 3-1
10KS 3-1
Input
Rated current
(3phase) with
20pcs battery
(2)
NA
NA
NA
NA
19A
22A
Frequency
≤
60% rated load: 40-70Hz
>
60% rated load: 45-55Hz (50Hz system)/54-66Hz (60Hz system)
Charging
current
(1)
Range
1~4A
2~12A
1~4A
2~12A
1~4A
2~12A
Default
1.4A
4A
2A
4A
2A
4A
Output
Rated voltage
(Phase voltage)
220/230/240VAC
Overload on
normal mode
105%-125% Load, 10 minutes transfer to Bypass;
125%-150% Load, 30 seconds transfer to Bypass;
>150% Load, 0.5 seconds transfer to Bypass
Short-circuit
current on normal
mode
54A for
200ms max
54A for
200ms max
113A for
200ms max
113A for
200ms max
113A for
200ms max
113A for
200ms max
Transfer Time Line<->Battery
0ms
Transfer Time INV<->Bypass
0ms
Battery
Battery Voltage
192/240VDC selectable
Battery Number
16/20PCS selectable
Environment
Ambient temperature
0°C ~ 50°C (Derating 50% above 40°C)
Relative humidity
0 ~ 95%(no condensing)
Operating altitude
<3000m (Derating use above 1km, the load should de-rating 1% every up 100m)
Storage temperature
(with battery)
-15°C ~ 40°C
Storage temperature
(without battery)
-25°C ~ 55°C
Criterion
Safety
IEC/EN 62040-1
EMC
IEC/EN 62040-2
Performance
IEC/EN 62040-3
(1)
In CVCF mode, UPS needs to be de-rated to 60% capacity (rated output power and maximum charging
current).
(2)
@ 220VAC input phase voltage, rated output power and maximum charging.