If the system must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -25°C to +55°C without battery (-15°C to
+40°C with battery).
TN-S/IT/TN-C/TT of electrical supply system may be connected by UPS.
This UPS may be provided with a maximum of 6 extension battery cabinets or equivalent.
Special precautions
The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling
operations.
All handling operations will require at least two people (unpacking, lifting, installation in
rack system).
Before and after the installation, if the UPS remains de-energized for a long period, the
UPS must be energized for a period of 24 hours, at least once every 6 months (for a normal
storage temperature less than 25°C). This charges the battery, thus avoiding possible
irreversible damage.
For three-phase AC input installation, this equipment complies with IEC 61000-3-12
provided that the short-circuit power Ssc is greater than or equal to 3.63MW at the
interface point between the user’s supply and the public system. It is the responsibility of
the installer or user of the equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to 3.63MW.
During the replacement of the Battery Module, it is imperative to use the same type and
number of elements as the original Battery Module provided with the UPS to maintain
an identical level of performance and safety.
This is a category C3 UPS product. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.