36 

6.

 

Communication 

6.1

 

RS232 and USB 

1. Communication cable to the serial or USB port on the computer. 
2. Connect the other end of the communication cable to the RS232 or USB 

communication port on the UPS. 

6.2

 

UPS remote control functions 

• 

Remote Power Off (RPO

 

When RPO is activated, UPS will cut off output immediately, and continues to alarm. 

 

RPO 

Comments 

Connector type 

16 AWG Maximum wires 

External breaker specification 

60 V DC/30 V AC 20 mA max 

Reset

 

1. Check the RPO connector status; 

2. Clear fault state through LCD. 

• 

Dry in 

Dry in function can be configured (see Settings > Dry in). 

 

Dry in 

Comments 

Connector type 

16 AWG Maximum wires 

External breaker specification 

60 V DC/30 V AC 20 mA max 

• 

Dry out 

Dry out is the relay out, dry out function can be configured (see Settings > Dry out). 

 

Dry out 

Comments 

Connector type 

16 AWG Maximum wires 

Inner Relay specification 

24Vdc/1A 

 
 
 
 
 
 

Summary of Contents for VFI 10000 ICR IoT

Page 1: ...PowerWalker VFI 6000 ICT ICR IoT VFI 10000 ICT ICR IoT Manual Uninterruptible Power Supply System EN...

Page 2: ...Service and support Call your local service representative...

Page 3: ...nd electronic equipment WEEE Indicates that the item must not be disposed of to the normal household waste but be separately collected and recycled Information advice help Refer to the user manual Saf...

Page 4: ...ting IP20 CAUTION To reduce the risk of fire the unit connects only to a circuit provided with branch circuit overcurrent protection The upstream circuit breaker for Normal AC Bypass AC must be easily...

Page 5: ...ss than 25 C This charges the battery thus avoiding possible irreversible damage For three phase AC input installation this equipment complies with IEC 61000 3 12 provided that the short circuit power...

Page 6: ...28 5 Operation 29 5 1 LCD panel 29 5 2 LCD description 31 5 3 Display functions 32 5 4 User settings 33 5 5 Starting the UPS with utility 34 5 6 Starting the UPS on Battery 34 5 7 UPS Shutdown 35 6 C...

Page 7: ...ost common power problems including power failures power sags power surges brownouts line noise high voltage spikes frequency variations switching transients and harmonic distortion Special characteri...

Page 8: ...l regulations for the disposal of packing materials Product The product is mainly made up of recyclable materials Dismantling and disassembly must take place in compliance with all local regulations c...

Page 9: ...x H x D mm UPS 1 1 Model RT 6KS 16 13 6 438 86 3 2U 540 RT 6KS 20 RT 10KS 16 15 5 RT 10KS 20 RT 6K 16 13 3 UPS 46 1 EBM UPS 438 86 3 2U 540 EBM 438 129 3U 559 RT 6K 20 13 3 UPS 56 1 EBM RT 10K 16 15 2...

Page 10: ...only RT 3 1 10K MBP For RT 3 1 model only Intelligent Card Dry Contact card AS400 See in chapter 6 5 NMC card MODBUS card CMC EMP Temperature and humidity sensors WLAN module WLAN module Wireless conn...

Page 11: ...5 2 2 Presentation 2 2 1 Tower model UPS modular Front view 1 Ventilation area 2 LCD Modular including 2 1 Button 2 2 LCD screen 2 3 LED indicator Tower UPS 6 10KS 1 1 Tower UPS 6 10K 1 1 10K S 3 1...

Page 12: ...el Slot 8 RJ45 for EBM detect 9 AC Input Output port Terminal Block 10 Input switch 11 External battery port 12 Maintenance bypass switch optional default is yes 6KS 1 1 10KS 1 1 6K 1 1 10K 1 1 10K 10...

Page 13: ...7 EBM External Battery Modular Front view 1 Ventilation area 2 EBM label Rear view 1 EBM port 1 2 EBM port 2 3 Fuse board cover replace EBM fuse 4 EBM detection Box RJ45 port...

Page 14: ...r Rear view 1 INTELLIGENT SLOT 2 RS232 3 Ethernet port RJ45 for IoT function 4 USB 5 Wireless HDMI For IoT function 6 RPO DRY in out 7 PARALLEL SLOT 8 RJ45 for EBM detect RT MBP detect 9 AC Input Outp...

Page 15: ...9 EBM External Battery Modular Front view 1 EBM label area 2 EBM label Rear view 1 Fuse board cover replace EBM fuse 2 EBM port 1 3 EBM port 2 4 EBM detection Box RJ45 port...

Page 16: ...pecting Unpacking the unit in a low temperature environment may cause condensation occurred in and on the cabinet Do not install the unit until the inside and outside of the unit are absolutely dry ha...

Page 17: ...erials must be disposed in compliance with all local regulations concerning waste 3 2 Checking the accessory kit Verify that the following additional items are included with the unit Tower model 1 1 m...

Page 18: ...O Optional default is Not configured 3 3 Mechanical Install 3 3 1 Tower model To keep air flowing freely it is recommended to keep a clearance with 500mm space both for front and rear side UPS model...

Page 19: ...ree space 500mm at least for front rear panels of the module 3 Do not carry the front rear panel of the module during installing Rack installing This procedure is suitable for 19 inch rack cabinet ins...

Page 20: ...sten the rail kit to the cabinet with 8pcs M5 screws washers as below 2 Install Rack ear to the unit by the M4 screws flat head 3 Slide the unit into rail kit and make sure tighten the rack mounting s...

Page 21: ...r this installing and it is recommended to be installed below to UPS 1 Install the rail kit if configured same as UPS as above 2 Install Rack ear to the unit by the M4 screws flat head 3 Slide the uni...

Page 22: ...irection 2 Set up the Tower foot then take the unit into Tower foot EBM model 1 Set up the Extension plate as below and install to Tower foot from UPS 2 Take the UPS EBM into Tower foot individually P...

Page 23: ...r device Before operating UPS input should cut off and check all terminals voltage to avoid voltage dangerous Backfeed contactor rating current should be larger than UPS rating input current Below fig...

Page 24: ...ngth of the output cable is recommended not to exceed 10 meters otherwise it may cause radio interference If a length of output cable over 10 meters requests please contact distributors agents for det...

Page 25: ...19 3 1 model This model support 2 modes setting as below default is setting with 3 1 mode 1 1 mode Short UPS input terminal L1 L2 L3 with busbar then connect AC cable 3 1 mode RT UPS 1 1 model...

Page 26: ...2 modes setting as below default is setting with 3 1 mode 1 1 mode Short UPS input terminal L1 L2 L3 with busbar then connect AC cable 3 1 mode For cables well fixed it is recommended to tie these cab...

Page 27: ...ecting the EBM 3 Before connecting the EBM make sure that the EBM specification is compatible with UPS configuration 4 Do not reverse the polarity of the external battery Connect with the configured E...

Page 28: ...UPS with Battery cable optional configured Tower model RT model Note 1 If additional battery cable needed for installation it must follow cable specification and the maximum length of battery cable 10...

Page 29: ...only RT MBP is RT UPS s optional modular UPS can be used with the MBP to implement the maintenance bypass switching function to ensure that the output of the system is not affected during the UPS main...

Page 30: ...nt When the distance between the load and the parallel UPS is less than 10 meters the length difference between the input output lines between the UPSs in the parallel system is less than 20 When the...

Page 31: ...25 Tower model parallel system 1 1 model 3 1 model 1 1 mode...

Page 32: ...26 3 1 mode RT model parallel system 1 1 model...

Page 33: ...27 3 1 model 1 1 mode 3 1 mode...

Page 34: ...system then the system will start to turn on and enter line mode 3 Regulate the output voltage of each UPS separately and check if the output voltage difference is less than 0 5V among the parallel sy...

Page 35: ...s events measurements and settings The LED Indicator Status Description Green On The UPS is operating normally on Online or on High Efficiency mode Orange On The UPS is on Battery mode Orange On The U...

Page 36: ...ection Exit the present menu Press to exit present menu to Main menu or the higher level menu without changing a setting Mute buzzer Press the button to mute the buzzer temporarily once new warning or...

Page 37: ...battery low This warning is approximate and the actual time to shutdown may vary significantly High Efficiency mode Once the mains are loss or abnormal the UPS would transfer to Line mode or Battery...

Page 38: ...ation and current alarms Event log Displays the events and faults stored Measurements Load W VA A P Input L1 Output V Hz Input L2 Input L3 V Hz if they exist Battery min V EBM DC Bus V Temperature Con...

Page 39: ...Enabled Auto restart Disabled Enabled Enabled Enabled Site wiring fault Enabled Disabled Disabled Overload pre alarm 50 105 105 External battery Auto detection Manual EBM 0 6 Manual Ah 0 300Ah Auto de...

Page 40: ...ith utility 5 6 Starting the UPS on Battery Before using this feature the UPS must have been powered by utility power with output enabled at least once Battery start can be disabled See the Cold start...

Page 41: ...35 5 7 UPS Shutdown...

Page 42: ...alarm RPO Comments Connector type 16 AWG Maximum wires External breaker specification 60 V DC 30 V AC 20 mA max Reset 1 Check the RPO connector status 2 Clear fault state through LCD Dry in Dry in fu...

Page 43: ...ss IoT Connection Wired network connection 1 Connect UPS to router or switch with network cable Please use CAT6 shielded network cable Make sure your IT settings can access the public network and Micr...

Page 44: ...d Ideal monitoring solution enables user to monitor and control the status of UPS on web browser via internet CMC card provides connection to Modbus protocol with standard RS485 signal AS400 G2 card P...

Page 45: ...ternet enter the serial No 511C1 01220 0100 478DF2A to install the software When you finish installation restart your computer the WinPower software will appear as a green plug icon located in the sys...

Page 46: ...never recharged over 6 months do not use them Contact your service representative 7 4 Recycle Contact your local recycling or hazardous waste center for information on proper disposal of the used equ...

Page 47: ...l through the listed events or faults 3 The following table describes typical conditions WARNING Problem Displayed Possible cause Remedy On Maintain Bypass Maintain bypass switch is open Check the mai...

Page 48: ...UPS and the ambient temperature DC bus or too high UPS internal fault the or DC BUS voltage is too high Consult dealer DC bus or too low UPS internal fault the or DC BUS voltage is too low Consult dea...

Page 49: ...ont panel display to silence the alarm Check the alarm condition and perform the applicable action to resolve the condition If the alarm status changes or press the ESC button 3s on the front panel di...

Page 50: ...KW 10KVA 10KW 10KVA 10KW 10KVA 10KW Rated frequency 50 60Hz Input Voltage range Phase voltage 110Vac 276Vac Rated voltage Phase voltage 220 230 240VAC Rated current 1phase with 16pcs battery 2 34A 42A...

Page 51: ...max 113A for 200ms max 113A for 200ms max 113A for 200ms max 113A for 200ms max Transfer Time Line Battery 0ms Transfer Time INV Bypass 0ms Battery Battery Voltage 192 240VDC selectable Battery Numbe...