33
Identification
[Model name], [Serial number], [firmware version],
[comm card firmware], [IP/MAC address]
5.4
User settings
Submenu
Available settings
Default settings
Password
Can be changed by user
4732
Language
English, Italiano, Français, Deutsch, Español,
Русский,
Polski,
简体中文
English
User password
[Enabled, ****], [Disabled]
Enabled
Audible alarms
[Enabled], [Disabled]
Enabled
Output voltage
[220V], [230V], [240V]
[230V]
[240V] for AU
Output frequency
[Autosensing], [converter 50Hz, 60Hz]
Autosensing
High efficiency
[Disabled], [Enabled]
Disabled
Auto bypass
[Disabled], [Enabled]
Enabled
Start/Restart
Cold start : [Disabled], [Enabled]
Auto restart : [Disabled], [Enabled]
Enabled
Enabled
Site wiring fault
[Enabled], [Disabled]
Disabled
Overload pre-alarm
[50%~105%]
105%
External battery
[Auto detection],
[Manual EBM: 0~6],
[Manual Ah: 0~300Ah]
Auto detection
0 EBM
0 Ah
Charger current
1-4A for 6-10k
2-12A for 6-10KS
1.4A for 6K
2A for 10K
4A for 6-10KS
Dry in signal
[Disabled], [Remote on], [Remote off],
[Forced bypass]
Disabled
Dry out signal
[Load powered], [On bat], [Low bat], [Bat open],
[Bypass], [UPS OK]
Bypass
Ambient temperature alarm [Enabled], [Disabled]
Enabled
Battery remaining time
[Enabled], [Disabled]
Enabled
Date and time
dd/mm/yyyy
hh:mm
01/01/2020
00:00
LCD contrast
[0-100%]
50%
Modbus TCP
[Enabled], [Disabled]
Disabled
IoT Enable
[Yes], [No]
No
Note:
if the utility power is IT system, the site wiring fault function should be disabled.