This selection is used for Integrated Site Testing. By default, after each component test (meter,
CT, PT, etc.) results are displayed, the PowerMaster
®
will wait for customer input. This allows the
user to retest or cancel the test altogether. If this selection is unchecked, the PowerMaster
®
will
verify the results meet the required specifications (see
Section 13.9.1
for Error Limits) and move
forward to the next test. If the results do not meet the required specifications, the PowerMaster
®
will stop and wait for customer input.
Enable Audio Feedback & Language
This selection allows the user to turn the audio off (unchecked) and on (checked). The volume
can be increased or decreased for both the general audio and the meter pulse. “Language”
allows the user to select the language preference for text displayed.
Backlight
Sets how long the backlight will stay on.
Stablize Load Box Phases
If checked, the load box(if installed) will attempt to stabilize all three phases at a higher precision.
If encountering errors, uncheck the box. Default value is unchecked.
Enable Load Box Logging
Checking this box enables the load box (if installed) to log any errors internally.
Meter Warmup Time
This determines the warm up time for the meter under test, measured in seconds.
Calibration Warmup Time
How long the 3302 operates before being ready for calibration
THD Stabilization Threshold
Adjustable from 1 to 100, default value is 5. Allows the load box to operate in areas of higher
THD due to the load.
CT
There are two options for how to display the parallelogram: Absolute Data, Relative to Zero
Burden. Below that are the options that determine which parallelogram is used:
1. IEEE: 2 Parallelograms at the CT rated accuracy levels (default is 0.3% and 0.6%)
2. User Defined: Takes into account the error limits the user defined on Page 1. Example,
3x error limit will draw a parallelogram at 0.9% and 1.8%
3. Both: Will draw a total of 4 parallelograms based on IEEE and User Defined.
Enable Pass/Fail
Unchecking this box turns off the pass/fail indicator and just returns data as it.