3.4.3
AC and DC wire selection
The following tables will help the installer to select AC and DC wires
PVI-3.8-I-OUTD
AWG
167°F
(75°C)
AWG
194°F
(90°C)
DC input wiring
PVI-3.8-I-OUTD
8-6
10-6
Ground
PVI-3.8-I-OUTD
4
4
AC output wiring
PVI-3.8-I-OUTD
8-6
10-6
Main ground
PVI-3.8-I-OUTD
6
6
PVI-4.6-I-OUTD
AWG
167°F
(75°C)
AWG
194°F
(90°C)
DC input wiring
PVI-4.6-I-OUTD
8-6
10-6
Ground
PVI-4.6-I-OUTD
4
4
AC output wiring
PVI-4.6-I-OUTD
8-6
8-6
Main ground
PVI-4.6-I-OUTD
6
6