Installation and operating manual
Page 21 of 95
(PVI-3.8/4.6-I-OUTD Rev.: 1.5)
Fig. 4 - Installation location - Minimum clearances around the inverter
RECOMMENDED POSITIONING
Fig. 5 - Recommended installation of AURORA inverters
NOTE: Although titled mounting is possible (see Fig. 6), please note that
this may reduce performance (Derating), due to a reduction in heat
dissipation.
WARNING: During operation, the unit surface may become very hot. To
avoid burns, DO NOT touch the surface.
200mm (8”)
150mm (6”)
150mm
.(6”)
50mm
(2”)