Installation and operating manual
Page 91 of 95
(PVI-3.8/4.6-I-OUTD Rev.: 1.5)
8.2
Output values
Description
Value
PVI–3.8-I-OUTD(-S)
Value
PVI–4.6-I-OUTD(-S)
Rated output power
3800 W
4600 W
Grid voltage, maximum
operating range
180 / 264 Vac (*)
Grid voltage, rated
230V
Grid frequency,
maximum range
47 / 63 Hz
Grid frequency, rated
50Hz
Rated output current
16.5 A
20 A
Max. output current
18.2 A
(16 A for UK Version
G83/1)
22.5 A
Output over current
protection
20 A
25 A
Maximum output fault
current
< 25A rms (60ms)
Inrush Current
negligible
Power factor range
-0.8 to +0.8
(*) Grid voltage, maximum operating range for Australia (AS47773): 200 / 264 Vac
WARNING: In case of more than an inverter are linked to the same
connection grid point, It will not be possible to avoid an unbalance of power
on three the phases, in fact the functioning of each device is independent
from the others. (Each inverter will feed the grid with the maximum power it
is able to supply).