Installation and operating manual
Page 90 of 95
(PVI-3.8/4.6-I-OUTD Rev.: 1.5)
Description
Value
PVI–3.8-I-OUTD(-S)
Value
PVI–4.6-I-OUTD(-S)
Maximum input power
4400 W
5260 W
Rated input power
4000 W
4800 W
Rated input voltage
330 Vdc
Max. absolute input
voltage
520 Vdc
Input voltage, MPPT
operating range
from 90 Vdc to 520 Vdc
Input voltage, MPPT
operating range at full
power
from 160 Vdc to 470
Vdc
from 180 Vdc to 470
Vdc
Max short circuit current
(of each array)
15.6 Adc
17 Adc
Max. operating input
current (of each array)
12.5 Adc
14 Adc
Maximum Backfeed
current (from AC to DC
side)
negligible
Max. input power (of
each array)
(1)
3000 W
PV ground fault
protection
Isolation detection PTC
Input channel
configuration (array)
Parallel / Independent
(2)
(1
) The total input power must remain within the max. recommended DC power value
(2)
The independent channel configuration cannot be used with positive grounding
setting or with floating photovoltaic generator
NOTE: If the photovoltaic field connected to the inverter supplies an input
current which is greater than the maximum usable value, the inverter will not
be damaged as long as the input voltage is within the permitted range.