4 Description of the product
4.1
Operating principle
4.1.1
Description of the function of the air pressure monitor
1
Air pressure monitor
2
Venturi
During pre-purge, the air pressure switch (differential pressure switch) is
interrogated. If the factory-set differential pressure of 6 mbar between
measuring points 1 and 2 is not reached, the lockout occurs (error
message "162 Air pressure switch") and the boiler is locked.
Possible causes:
blocked siphon
blocked flue gas pipe
blocked air filter
blocked suction pipe
For more information, see
4.2
Main components