Start of holiday (642 - 662)
Entering the holiday start.
End of holiday (643 - 663)
Entering the holiday end.
Operating level (648-668)
Selection of the operating level (Reduced or Protection) for the holiday
programme
Important
A holiday period always ends on the last day at 12:00 AM (23:59).
The holiday programmes are only activated in the operation mode
Automatically.
See
See also the User manual EC five.
9.2.6
Heating circuits
Operating mode (700, 1000, 1300)
The operating mode can be set via the operation mode button at the boiler
or at the room device. For other service tools, the operating mode is set
via this control line.
Protection: The heating is switched off in protection mode. The room
remains protected against frost however (Frost protection setpoint, e.g.
prog. no. 714).
Automatic: In automatic mode, the room temperature is controlled in
accordance with the time program that is selected.
Reduced: In reduced operation mode the room temperature is kept
constantly to the set Reduced setpoint(e.g. prog. no. 712).
Comfort: In comfort mode the room temperature is kept constantly to the
set Comfort setpoint(e.g. prog. no. 710). Eco functions are not activated.
Comfort setpoint (710, 1010, 1310)
Setting of the comfort setpoint in the heating phases. Without room sensor
or with the room influence switched off (prog.no. 750, 1050, 1350), this
value is used for calculation of the flow temperature, to theoretically reach
the set room temperature.
Reduced setpoint (712, 1012, 1312)
Setting of the desired room temperature during the reduced heating
phase. Without room sensor or with the room influence switched off
(prog.no. 750, 1050, 1350), this value is used for calculation of the flow
temperature, to theoretically reach the set room temperature.
Frost protection setpoint (714, 1014, 1314)
Setting of the required room temperature during frost protection mode.
Without room sensor or with the Room influence(prog.no. 750, 1050,
1350), this value is used for calculation of the flow temperature, to
theoretically reach the set room The heating circuit remains turned off until
the flow temperature drops so far that the room temperature falls below
the frost protection temperature.
Heating curve slope (720, 1020, 1320)
Using the heating curve, the flow temperature setpoint is formed that is
used to regulate the heating circuit, subject to the outside temperature.
The gradient indicates how much the flow temperature changes by with
changing outside temperature.
9 Settings
86
7703301 - 01 - 16072018