Delete all devices (140)
The wireless connections to all units is cancelled here.
9.2.4
Time programs
General information about the time programs.
Important
Time programs 1 and 2 are always assigned to the respective
heating circuits (1 and 2) and only displayed if these heating
circuits are present and also turned on in the menu Configuration
(prog.-no. 5710 and 5715).
Time program 3 can be used for heating circuit 3, for the DHW and for the
circulation pump, depending on the setting, and is always displayed.
Time program 4 can be used for the DHW and for the circulation pump,
depending on the setting, and is always displayed.
Time program 5 is not assigned a function and can be freely used for any
application using an output QX.
Preselection (500 – 600)
Selection of weekday or day blocks. The day blocks (Mon-Sun, Mon-Fri
and Sat-Sun) assist the adjustment. The set times are only copied to the
individual weekdays and can be changed in the individual day settings as
required.
The times of the individual weekdays always determine the heating
program.
Important
If a time in a group of days is changed, all 3 start/stop phases will
be copied to the day group automatically.
To select groups of days (Mon-Sun, Mon-Fri or Sat-Sun), turn the
control knob anti-clockwise; to select individual days (Mon, Tue,
Wed, Thu, Fri, Sat, Sun), turn the control knob clockwise.
Heating phases (501 — 606)
Up to 3 heating phases can be set per heating circuit. These are active on
the days selected under Preselection (prog.no. 500, 520, 540, 560, 600).
During the heating phases the system heats to the set comfort setpoint.
Outside the heating phases, the system heats to the reduced setpoint.
Important
The time programs are only activated in Automatically operating
mode.
Copy? (515–615)
The time program for one day can be copied and assigned to another or
several other days.
Important
Day blocks cannot be copied.
Default values (516–616)
Setting of the default values given in the setting table
9.2.5
Holiday programs
Preselection (641 - 661)
Important
The heating circuits may be set to a selectable operation level with
the holiday programme during a certain holiday period.
8 holiday periods can be selected with this preselection.
9 Settings
7703301 - 01 - 16072018
85