Diagnostics consumers
Prog. no.
Level Standard value
Relay output QX21 module 2
0: Off | 1: On
9053
C
Relay output QX22 module 2
0: Off | 1: On
9054
C
Relay output QX23 module 2
0: Off | 1: On
9055
C
Relay output QX21 module 3
0: Off | 1: On
9056
C
Relay output QX22 module 3
0: Off | 1: On
9057
C
Relay output QX23 module 3
0: Off | 1: On
9058
C
Prog. no.
Level
Standard value
Prepurge time
9500
E
20 s
Required output prepurging
9504
E
EC five 125 kW: 100
kW
EC five 170 kW: 120
kW
EC five 215 kW: 100
kW
EC five 260 kW: 180
kW
EC five 300 kW: 170
kW
Required output ignition
1)
9512
E
EC five 125 kW: 59.3
kW
EC five 170 kW: 75.5
kW
EC five 215 kW: 77.1
kW
EC five 260 kW: 97.7
kW
EC five 300 kW:
103.9 kW
Required output LF
1)
9524
E
EC five 125 kW: 20
kW
EC five 170 kW: 28
kW
EC five 215 kW: 35
kW
EC five 260 kW: 42
kW
EC five 300 kW: 48
kW
Required output HF
1)
9529
E
EC five 125 kW: 125
kW
EC five 170 kW: 170
kW
EC five 215 kW: 215
kW
EC five 260 kW: 260
kW
EC five 300 kW: 300
kW
Postpurge time
9540
E
20 s
9 Settings
7703301 - 01 - 16072018
81