34
8.2.4.4
Set error behaviour of outputs
FOU1
Select and define value
On
= Output 1 is switched
ON
in the case of a fault.
OFF
= Output 1 is switched
OFF
in the case of a fault.
> For both values –
ON
and
OFF
– the counter does not continue to
add in the case of an error.
OU
= Output 1 operates irrespective of the error case as defined with
the parameters
FOU2
Select and define value
On
= Output 2 is switched
ON
, in the case of a fault, the analog
signal goes to the upper limit value (22 mA).
OFF
= Output 2 is switched
OFF
in the case of a fault, the analog
signal goes to the lower limit value (3.5 mA).
OU
= Output 2 operates irrespective of the error case as defined
with the parameters. The course of the analog signal corresponds
with IEC60947-5-7.
12
-30% -20%
0%
100% 120% 130%
13
3
Output characteristic according to analog output according to standard
IEC 60947-5-7
1: Output current in mA
2: Working range
3: Measuring range
4: Area between analog starting point and analog end point
5: Error message [Err.] is displayed
6: Measuring range end value
7: Error message [OL] is indicated (= overload)
8 Progr Parameter setting